Honeywell Safety Manager
Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.
describes (4)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2022-30316US | medium6.8OT elevated | — | ||
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthe… | ||||
| CVE-2022-30315US | critical9.8OT elevated | — | ||
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion… | ||||
| CVE-2022-30314US | medium4.6OT elevated | — | ||
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. T… | ||||
| CVE-2022-30313US | high7.5OT elevated | — | ||
Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety M… | ||||
references
External citations — patches, advisories, analysis.
- ICS Advisory ICSA-22-207-02 JSONself
- Recommended Practicesexternal
- ICSA Advisory ICSA-22-207-02 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
remediations (8)
- MitigationSafety Manager
(CVE-2022-30313) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.
- MitigationSafety Manager
(CVE-2022-30314) Customers should isolate process control networks following our security best practices.
- MitigationSafety Manager
(CVE-2022-30315) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.
- MitigationSafety Manager
Honeywell has identified the following specific workarounds and mitigations users can apply to reduce risk:
- FixedSafety Manager
(CVE-2022-30313) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.
- FixedSafety Manager
(CVE-2022-30314) Safety Manager R160.1 and later releases include a remediation for this item. R160.1 was introduced in October 2014. Users are advised to operate on the latest release and point release.
https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-manager - FixedSafety Manager
(CVE-2022-30315) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.
- FixedSafety Manager
(CVE-2022-30316) The Safety Manager key switch prevents unauthorized firmware from being installed. Users are advised to monitor the key switch position.