CVE-2022-30316
mediumpriority · track · 27OT risk · elevatedEPSS 0.004 · 32 %ileEURUUSEPSS · scored 2026-10-28
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthenticated firmware update issue. The affected components are characterized as: Firmware update functionality. The potential impact is: Firmware manipulation. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 communication FTA serial interface and Enea POLO bootloader for firmware management purposes. An engineering workstation running the Safety Builder software communicates via serial or serial-over-ethernet link with the DCOM-232/485 interface. Firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. Firmware images are unsigned. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize hardcoded credentials (see FSCT-2022-0052) for the POLO bootloader to control the boot process and push malicious firmware images to the controller allowing for firmware manipulation, remote code execution and denial of service impacts. A mitigating factor is that in order for a firmware update to be initiated, the Safety Manager has to be rebooted which is typically done by means of physical controls on the Safety Manager itself. As such, an attacker would have to either lay dormant until a legitimate reboot occurs or possibly attempt to force a reboot through a secondary vulnerability.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSafety Managercisa_csaf_ot
(CVE-2022-30316) The Safety Manager key switch prevents unauthorized firmware from being installed. Users are advised to monitor the key switch position.
- MitigationSafety Managercisa_csaf_ot
Honeywell has identified the following specific workarounds and mitigations users can apply to reduce risk:
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–critical · 6.2–9.8
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (6)
Products and version ranges known to be affected.
- honeywell safety manager firmwareall versionsnvdUScpe:2.3:o:honeywell:safety_manager_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-22-207-02Honeywell Safety Manager2022-07-26icsa · cisa_csaf_otUS
Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (11)
External citations — patches, advisories, analysis.
- https://cxsecurity.com/cveshow/CVE-2022-30316/cnnvd
- https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-managerPatchcnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-207-02cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.3668cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022072707cnnvd
- https://www.forescout.com/blog/cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02enisa_euvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan