CVE-2022-30314
mediumpriority · track · 18OT risk · elevatedEPSS 0.003 · 22 %ileEURUUSEPSS · scored 2026-10-28
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSafety Managercisa_csaf_ot
(CVE-2022-30314) Safety Manager R160.1 and later releases include a remediation for this item. R160.1 was introduced in October 2014. Users are advised to operate on the latest release and point release.
https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-manager - MitigationSafety Managercisa_csaf_ot
(CVE-2022-30314) Customers should isolate process control networks following our security best practices.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.2–7.5
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (6)
Products and version ranges known to be affected.
- honeywell safety manager firmware< r160.1nvdUScpe:2.3:o:honeywell:safety_manager_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-22-207-02Honeywell Safety Manager2022-07-26icsa · cisa_csaf_otUS
Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (11)
External citations — patches, advisories, analysis.
- https://cxsecurity.com/cveshow/CVE-2022-30314/cnnvd
- https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-managerPatchcnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-207-02cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.3668cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022072708cnnvd
- https://www.forescout.com/blog/cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02enisa_euvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.