CVE-2022-30313
highpriority · track · 30OT risk · elevatedEPSS 0.009 · 61 %ileEURUUSEPSS · scored 2026-10-28
Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety Manager multiple proprietary protocols with unauthenticated functionality issue. The affected components are characterized as: Honeywell Experion TCP (51000/TCP), Safety Builder (51010/TCP). The potential impact is: Manipulate controller state, Manipulate controller configuration, Manipulate controller logic, Manipulate controller files, Manipulate IO. The Honeywell Experion PKS Distributed Control System (DCS) Safety Manager utilizes several proprietary protocols for a wide variety of functionality, including process data acquisition, controller steering and configuration management. These protocols include: Experion TCP (51000/TCP) and Safety Builder (51010/TCP). None of these protocols have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocols in question. An attacker capable of invoking the protocols' functionalities could achieve a wide range of adverse impacts, including (but not limited to), the following: for Experion TCP (51000/TCP): Issue IO manipulation commands, Issue file read/write commands; and for Safety Builder (51010/TCP): Issue controller start/stop commands, Issue logic download/upload commands, Issue file read commands, Issue system time change commands. A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedSafety Managercisa_csaf_ot
(CVE-2022-30313) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.
- MitigationSafety Managercisa_csaf_ot
(CVE-2022-30313) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (6)
Products and version ranges known to be affected.
- honeywell safety manager firmwareall versionsnvdUScpe:2.3:o:honeywell:safety_manager_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-22-207-02Honeywell Safety Manager2022-07-26icsa · cisa_csaf_otUS
Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (11)
External citations — patches, advisories, analysis.
- https://cxsecurity.com/cveshow/CVE-2022-30313/cnnvd
- https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-managerPatchcnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-207-02cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.3668cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022072707cnnvd
- https://www.forescout.com/blog/cnnvd
- https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02enisa_euvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan