CVE-2025-24510
mediumpriority · track · 0EPSS 0.003 · 19 %ileDEEUNLUSEPSS · scored 2026-10-27
A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
The vendor does not plan to fix this; mitigate or replace.
- No fix plannedMS/TP Point Pickup Modulesiemens_psirt
Currently no fix is planned
- No fix plannedMS/TP Point Pickup Modulecisa_csaf_ot
Currently no fix is planned
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.9–7.1
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (548)
Products and version ranges known to be affected.
advisories (3)
Vendor and ecosystem advisories describing this.
- NCSC-2025-0160Kwetsbaarheden verholpen in Siemens productenNL2025-05-14csaf · ncsc_nlNL
Siemens heeft kwetsbaarheden verholpen in diverse producten als Apogee, BacNet ATEC, Desigo CC, Intralog, OZW, Polarion, RUGGEDCOM, SICAM, SIMATIC, SIPROTEC, SIRIUS, Teamcenter en Versicharge
- SSA-668154SSA-668154: Denial of Service Vulnerability in MS/TP Point Pickup Module2025-05-13csaf · siemens_psirtDE
MS/TP Point Pickup Module devices are affected by a denial of service vulnerability that could be triggered by an attacker residing in the same BACnet network by sending a specially crafted MSTP message. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
- ICSA-25-135-16Siemens MS/TP Point Pickup Module2025-05-13icsa · cisa_csaf_otUS
MS/TP Point Pickup Module devices are affected by a denial of service vulnerability that could be triggered by an attacker residing in the same BACnet network by sending a specially crafted MSTP message. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
also known as (3)