Siemens MS/TP Point Pickup Module
view advisory published 2025-05-13
MS/TP Point Pickup Module devices are affected by a denial of service vulnerability that could be triggered by an attacker residing in the same BACnet network by sending a specially crafted MSTP message. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
01
describes (1)
Related CVEs.
| ID | severity | exploitable | ||
|---|---|---|---|---|
| CVE-2025-24510US | — | — | ||
A vulnerability has been identified in MS/TP Point Pickup Module (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an atta… | ||||
02
references
External citations — patches, advisories, analysis.
- SSA-668154: Denial of Service Vulnerability in MS/TP Point Pickup Module - CSAF Versionself
- SSA-668154: Denial of Service Vulnerability in MS/TP Point Pickup Module - HTML Versionself
- ICS Advisory ICSA-25-135-16 JSONself
- Recommended Practicesexternal
- ICS Advisory ICSA-25-135-16 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
03
remediations (1)
- No fix plannedMS/TP Point Pickup Module
Currently no fix is planned
scry
Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.
Free scan