ICSA-26-202-10

icsaUScisa_csaf_ot

Rockwell Automation Studio 5000 Logix Designer

view advisory published 2026-07-21

Successful exploitation of these vulnerabilities could allow for a local attacker to execute arbitrary files, alter configurations, or execute arbitrary code.

01

describes (3)

Related CVEs.

IDseverity exploitable
CVE-2026-9128UShigh7.5—
A code execution security issue exists within Studio 5000 Logix Designer® due to an unquoted search path in the External Tools configuration. The executable paths specified in the…
CVE-2026-9127UShigh7.5OT elevated—
A remote code execution security issue exists within Studio 5000 Logix Designer® due to incorrect authorization on a configuration file. This can allow any authenticated user to mo…
CVE-2026-9108UShigh7.5—
A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or valid…
02

references

External citations — patches, advisories, analysis.

03

remediations (6)

  • MitigationStudio 5000 Logix Designer

    Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell Automation's security best practices (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight).

    https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
  • MitigationStudio 5000 Logix Designer

    Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell Automation's security best practices (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight).

    https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
  • MitigationStudio 5000 Logix Designer

    Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use Rockwell Automation's security best practices (https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight).

    https://support.rockwellautomation.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
  • FixedStudio 5000 Logix Designer

    Rockwell Automation recommends users to upgrade to the following: Studio 5000 Logix Designer: V37.00, 36.01, 35.02, 34.04, 33.04, 32.05 (CVE-2026-9108)

  • FixedStudio 5000 Logix Designer

    Studio 5000 Logix Designer: V36.00, 35.01, 34.02, 33.02, 32.05 (CVE-2026-9127)

  • FixedStudio 5000 Logix Designer

    Studio 5000 Logix Designer: V36.00, 35.01, 34.03, 33.03, 32.05 (CVE-2026-9128)