CVE-2024-6242
highpriority · track · 4EPSS 0.111 · 96 %ileDEEURUUSEPSS · scored 2026-10-26
A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- Fixed1756-EN4TRcisa_csaf_ot
1756-EN4TR: Update to versions V5.001 and later.
https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111 - FixedControlLogix 5580 (1756-L8z)cisa_csaf_ot
ControlLogix 5580 (1756-L8z): Update to versions V32.016, V33.015, V34.014,V35.011 and later.
https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111 - Mitigation1756-EN2F, Series A/B (signed version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2F, Series A/B (unsigned version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2F, Series Ccisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2T, Series A/B/C (signed version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2T, Series A/B/C (unsigned version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2T, Series Dcisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2TP, Series Acisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2TR, Series A/B (signed version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2TR, Series A/B (unsigned version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN2TR, Series Ccisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN3TR, Series A (signed version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN3TR, Series A (unsigned version)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN3TR, Series Bcisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- Mitigation1756-EN4TRcisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- MitigationControlLogix 5580 (1756-L8z)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- MitigationGuardLogix 5580 (1756-L8zS)cisa_csaf_ot
Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.5–8.4
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (65)
Products and version ranges known to be affected.
advisories (2)
Vendor and ecosystem advisories describing this.
- WID-SEC-W-2024-1747Rockwell Automation ControlLogix: Schwachstelle ermöglicht Umgehen von SicherheitsvorkehrungenDeutsch2024-08-01csaf · cert_bundDE
Ein entfernter, authentisierter Angreifer kann eine Schwachstelle in Rockwell Automation ControlLogix ausnutzen, um Sicherheitsvorkehrungen zu umgehen.
- ICSA-24-214-09Rockwell Automation Logix Controllers2024-08-01icsa · cisa_csaf_otUS
Successful exploitation of this vulnerability could allow an attacker to execute CIP programming and configuration commands.
also known as (5)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (4)
External citations — patches, advisories, analysis.
- https://cxsecurity.com/cveshow/CVE-2024-6242/cnnvd
- https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.htmlcnnvd
- https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.htmlenisa_euvd
- https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1682.htmlnvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.