CVE-2024-6242

highpriority · track · 4EPSS 0.111 · 96 %ileDEEURUUS
grimoire priorityP1 · Urgent
Exploitable?
—
no known exploitation
Likely / severe?
11.1% (96th) EPSS
CVSS 8.4 · high
Is it mine?
65 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-26

A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • Fixed1756-EN4TRcisa_csaf_ot

    1756-EN4TR: Update to versions V5.001 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
  • FixedControlLogix 5580 (1756-L8z)cisa_csaf_ot

    ControlLogix 5580 (1756-L8z): Update to versions V32.016, V33.015, V34.014,V35.011 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
  • Mitigation1756-EN2F, Series A/B (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series A/B (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series Ccisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series Dcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TP, Series Acisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series Ccisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (signed version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (unsigned version)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series Bcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN4TRcisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationControlLogix 5580 (1756-L8z)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationGuardLogix 5580 (1756-L8zS)cisa_csaf_ot

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

02

cvss

Technical severity, 0–10. One row per scoring source.

8.4
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.5–8.4

v3.18.4highCVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:C/C:L/I:H/A:Hsecondary · CISA US
v3.18.4highAV:N/AC:H/PR:L/UI:N/S:C/C:L/I:H/A:Hsecondary · FSTEC (BDU) RU
v4.07.3highCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:Hsecondary · ENISA EU
v4.07.3highCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · PSIRT@rockwellautomation.com
v4.04.5mediumCVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:H/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (65)

Products and version ranges known to be affected.

showing 20 of 65
06

advisories (2)

Vendor and ecosystem advisories describing this.

  • WID-SEC-W-2024-1747Rockwell Automation ControlLogix: Schwachstelle ermöglicht Umgehen von SicherheitsvorkehrungenDeutsch2024-08-01csaf · cert_bundDE

    Ein entfernter, authentisierter Angreifer kann eine Schwachstelle in Rockwell Automation ControlLogix ausnutzen, um Sicherheitsvorkehrungen zu umgehen.

  • ICSA-24-214-09Rockwell Automation Logix Controllers2024-08-01icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability could allow an attacker to execute CIP programming and configuration commands.

07

also known as (5)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (4)

External citations — patches, advisories, analysis.