ICSA-24-214-09

icsaUScisa_csaf_ot

Rockwell Automation Logix Controllers

view advisory published 2024-08-01

Successful exploitation of this vulnerability could allow an attacker to execute CIP programming and configuration commands.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2024-6242US——
A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any af…
02

references

External citations — patches, advisories, analysis.

03

remediations (18)

  • Mitigation1756-EN2F, Series A/B (signed version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series A/B (unsigned version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2F, Series C

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (signed version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series A/B/C (unsigned version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2T, Series D

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TP, Series A

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (signed version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series A/B (unsigned version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN2TR, Series C

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (signed version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series A (unsigned version)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN3TR, Series B

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Mitigation1756-EN4TR

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationControlLogix 5580 (1756-L8z)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • MitigationGuardLogix 5580 (1756-L8zS)

    Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.

  • Fixed1756-EN4TR

    1756-EN4TR: Update to versions V5.001 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
  • FixedControlLogix 5580 (1756-L8z)

    ControlLogix 5580 (1756-L8z): Update to versions V32.016, V33.015, V34.014,V35.011 and later.

    https://compatibility.rockwellautomation.com/Pages/MultiProductSelector.aspx?crumb=111
scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan