CVE-2017-12069

mediumpriority · track · 34EPSS 0.029 · 87 %ileDEEUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
2.90% (87th) EPSS
CVSS 6.4 · medium
Is it mine?
23 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · cisa_csaf_ot · nvd

EPSS · scored 2026-10-24

An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedSIMATIC IT Production Suitesiemens_psirt

    Update to V7.1 or later version

  • FixedSIMATIC NET PC Software V14siemens_psirt

    Update to V14 SP1 Update 14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109807351/
  • FixedSIMATIC WinCC Runtime Professional V14siemens_psirt

    Update to V14 SP1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109746276
  • FixedSIMATIC IT Production Suitecisa_csaf_ot

    Update to V7.1 or later version

  • FixedSIMATIC NET PC Software V14cisa_csaf_ot

    Update to V14 SP1 Update 14 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109807351/
  • FixedSIMATIC WinCC Runtime Professional V14cisa_csaf_ot

    Update to V14 SP1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109746276
  • MitigationSIMATIC IT Production Suitesiemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC NET PC Software V14siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC PCS 7siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCCsiemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V13siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V14siemens_psirt

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC IT Production Suitecisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC NET PC Software V14cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC PCS 7cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCCcisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V13cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • MitigationSIMATIC WinCC Runtime Professional V14cisa_csaf_ot

    Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461

  • No fix plannedSIMATIC PCS 7siemens_psirt

    Currently no fix is planned

  • No fix plannedSIMATIC WinCCsiemens_psirt

    Currently no fix is planned

  • No fix plannedSIMATIC WinCC Runtime Professional V13siemens_psirt

    Currently no fix is planned

  • No fix plannedSIMATIC PCS 7cisa_csaf_ot

    Currently no fix is planned

  • No fix plannedSIMATIC WinCCcisa_csaf_ot

    Currently no fix is planned

  • No fix plannedSIMATIC WinCC Runtime Professional V13cisa_csaf_ot

    Currently no fix is planned

02

cvss

Technical severity, 0–10. One row per scoring source.

8.2
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.4–8.2

v2.06.4mediumAV:N/AC:L/Au:N/C:P/I:N/A:Pprimary · NVD / NIST USexploitability 10 · impact 4.9
v3.08.2highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 4.2
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.18.2highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.18.2highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (23)

Products and version ranges known to be affected.

05

advisories (2)

Vendor and ecosystem advisories describing this.

  • SSA-535640SSA-535640: Vulnerability in Industrial Products2017-08-30csaf · siemens_psirtDE

    Various industrial products use the Discovery Service of the OPC UA protocol stack by the OPC foundation https://github.com/OPCFoundation/UA-.NETStandard and could therefore be affected by the remote resource consumption attacks (CVE-2017-12069).

  • ICSA-17-243-01Siemens OPC UA Protocol Stack Discovery Service (Update E)2017-08-30icsa · cisa_csaf_otUS

    Various industrial products use the Discovery Service of the OPC UA protocol stack by the OPC foundation https://github.com/OPCFoundation/UA-.NETStandard and could therefore be affected by the remote resource consumption attacks (CVE-2017-12069).

06

also known as (3)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

09

references (10)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan