CVE-2025-40570

lowPriorität · verfolgen · 0EPSS 0.002 · 9. PerzentilDEEUNLUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
0.20% (9th) EPSS
CVSS 2.4 · low
Is it mine?
237 products
Prüfe deine Angriffsfläche
Who says so?
6 sources
cnnvd · enisa_euvd · cert_bund · cisa_csaf_ot

EPSS · bewertet 2026-10-26

A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V10.0), SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA82 (CP150) (All versions < V10.0), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD82 (CP150) (All versions < V10.0), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ81 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ82 (CP150) (All versions < V10.0), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SK82 (CP150) (All versions < V10.0), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL82 (CP150) (All versions < V10.0), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7ST85 (CP300) (All versions < V10.0), SIPROTEC 5 7ST86 (CP300) (All versions < V10.0), SIPROTEC 5 7SX82 (CP150) (All versions < V10.0), SIPROTEC 5 7SX85 (CP300) (All versions < V10.0), SIPROTEC 5 7SY82 (CP150) (All versions < V10.0), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT82 (CP150) (All versions < V10.0), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V10.0), SIPROTEC 5 7VU85 (CP300) (All versions < V10.0), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V10.0). Affected devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack. The protection function is not affected of this vulnerability.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

2.4
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen

v3.12.4lowCVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · productcert@siemens.com DEAusnutzbarkeit 0.9 · Auswirkung 1.4
v3.12.4lowCVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · CISA US
v3.12.4lowCVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · Siemens ProductCERT DE
v3.12.4lowCVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · NCSC-NL NL
v4.02.4lowCVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.02.4lowCVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.00.4lowCVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Trackcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (237)

Betroffene Produkte und Versionsbereiche.

06

Advisories (4)

Hersteller- und Ökosystem-Meldungen dazu.

  • NCSC-2025-0246Kwetsbaarheden verholpen in Siemens productenNL2025-08-12csaf · ncsc_nlNL

    Siemens heeft kwetsbaarheden verholpen in diverse producten als SIMATIC, SINEC, SIMAC, RUGGEDCOM, SIMOTION, SINAMICS, SIPROTEC en SINUMERIK.

  • SSA-894058SSA-894058: Improper Bandwidth Limitation of Network Packets Over Local USB Port Vulnerability in SIPROTEC 52025-08-12csaf · siemens_psirtDE

    Affected SIPROTEC 5 devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack and the protection function is not affected of this vulnerability. Siemens has released new versions for the affected products and recommends to update to the latest versions.

  • WID-SEC-W-2025-1768Siemens SIPROTEC: Mehrere Schwachstellen ermöglichen Denial of ServiceDeutsch2025-08-12csaf · cert_bundDE

    Ein entfernter, anonymer Angreifer oder ein Angreifer mit physischem Zugriff kann mehrere Schwachstellen in Siemens SIPROTEC ausnutzen, um einen Denial of Service Angriff durchzuführen.

  • ICSA-25-226-10Siemens SIPROTEC 52025-08-12icsa · cisa_csaf_otUS

    Affected SIPROTEC 5 devices do not properly limit the bandwidth for incoming network packets over their local USB port. This could allow an attacker with physical access to send specially crafted packets with high bandwidth to the affected devices thus forcing them to exhaust their memory and stop responding to any network traffic via the local USB port. Affected devices reset themselves automatically after a successful attack and the protection function is not affected of this vulnerability. Siemens has released new versions for the affected products and recommends to update to the latest versions.

07

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (3)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan