CVE-2025-40555
mediumPriorität · verfolgen · 0EPSS 0.002 · 12. PerzentilDEEUNLUSEPSS · bewertet 2026-10-27
A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Der Hersteller plant keinen Fix; mindern oder ersetzen.
- Kein Fix geplantAPOGEE PXC+TALON TC Series (BACnet)siemens_psirt
Currently no fix is planned
- Kein Fix geplantAPOGEE PXC+TALON TC Series (BACnet)cisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · low–medium · 1.3–5.3
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (548)
Betroffene Produkte und Versionsbereiche.
Advisories (3)
Hersteller- und Ökosystem-Meldungen dazu.
- NCSC-2025-0160Kwetsbaarheden verholpen in Siemens productenNL2025-05-14csaf · ncsc_nlNL
Siemens heeft kwetsbaarheden verholpen in diverse producten als Apogee, BacNet ATEC, Desigo CC, Intralog, OZW, Polarion, RUGGEDCOM, SICAM, SIMATIC, SIPROTEC, SIRIUS, Teamcenter en Versicharge
- SSA-718393SSA-718393: Partial Denial of Service Vulnerability in APOGEE PXC and TALON TC Series (BACnet) Devices2025-05-13csaf · siemens_psirtDE
APOGEE PXC and TALON TC Series (BACnet) Devices devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
- ICSA-25-135-14Siemens APOGEE PXC and TALON TC Series2025-05-13icsa · cisa_csaf_otUS
APOGEE PXC and TALON TC Series (BACnet) Devices devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
auch bekannt als (3)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (3)
Externe Belege — Patches, Meldungen, Analysen.
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan