CVE-2025-40555

mediumPriorität · verfolgen · 0EPSS 0.002 · 12. PerzentilDEEUNLUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
0.22% (12th) EPSS
CVSS 4.7 · medium
Is it mine?
548 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · cisa_csaf_ot · ncsc_nl

EPSS · bewertet 2026-10-27

A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Der Hersteller plant keinen Fix; mindern oder ersetzen.

  • Kein Fix geplantAPOGEE PXC+TALON TC Series (BACnet)siemens_psirt

    Currently no fix is planned

  • Kein Fix geplantAPOGEE PXC+TALON TC Series (BACnet)cisa_csaf_ot

    Currently no fix is planned

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

5.3
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · low–medium · 1.3–5.3

v3.14.7mediumCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Lsecondary · productcert@siemens.com DEAusnutzbarkeit 2.8 · Auswirkung 1.4
v3.14.7mediumCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Lsecondary · CISA US
v3.14.7mediumCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Lsecondary · Siemens ProductCERT DE
v3.14.7mediumCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Lsecondary · NCSC-NL NL
v4.05.3mediumCVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:Lsecondary · ENISA EU
v4.05.3mediumCVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.01.3lowCVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:L/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Trackcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (548)

Betroffene Produkte und Versionsbereiche.

06

Advisories (3)

Hersteller- und Ökosystem-Meldungen dazu.

  • NCSC-2025-0160Kwetsbaarheden verholpen in Siemens productenNL2025-05-14csaf · ncsc_nlNL

    Siemens heeft kwetsbaarheden verholpen in diverse producten als Apogee, BacNet ATEC, Desigo CC, Intralog, OZW, Polarion, RUGGEDCOM, SICAM, SIMATIC, SIPROTEC, SIRIUS, Teamcenter en Versicharge

  • SSA-718393SSA-718393: Partial Denial of Service Vulnerability in APOGEE PXC and TALON TC Series (BACnet) Devices2025-05-13csaf · siemens_psirtDE

    APOGEE PXC and TALON TC Series (BACnet) Devices devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.

  • ICSA-25-135-14Siemens APOGEE PXC and TALON TC Series2025-05-13icsa · cisa_csaf_otUS

    APOGEE PXC and TALON TC Series (BACnet) Devices devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.

07

auch bekannt als (3)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (3)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan