Siemens APOGEE PXC and TALON TC Series
APOGEE PXC and TALON TC Series (BACnet) Devices devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation. Siemens recommends countermeasures for products where fixes are not, or not yet available.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2025-40555US | — | — | ||
A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a s… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
- SSA-718393: Partial Denial of Service Vulnerability in APOGEE PXC and TALON TC Series (BACnet) Devices - CSAF Versionself
- SSA-718393: Partial Denial of Service Vulnerability in APOGEE PXC and TALON TC Series (BACnet) Devices - HTML Versionself
- ICS Advisory ICSA-25-135-14 JSONself
- Recommended Practicesexternal
- ICS Advisory ICSA-25-135-14 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
Behebungen (1)
- Kein Fix geplantAPOGEE PXC+TALON TC Series (BACnet)
Currently no fix is planned
Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan