CWE-610: Externally Controlled Reference to a Resource in Another Sphere vulnerability exists that could cause a loss of confidentiality when an unauthenticated attacker manipulates controller’s webserver URL to access resources.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenModicon Controllers LMC058cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • BehobenModicon Controllers M241cisa_csaf_ot

    Versions 5.3.12.48 of Modicon Controllers M241 include a fix for this vulnerability and can be downloaded here: M241:https://www.se.com/ww/en/product-range/62129-modicon-m241-micro-plc/#software-and-firmware * Use the Controller Assistant feature of EcoStruxure™ Automation Expert - Motion V24.1 or EcoStruxure™ Machine Expert V2.3 to update the M241/M251 firmware and perform a reboot. * EcoStruxure™ Automation Expert - Motion V24.1 and EcoStruxure™ Machine Expert V2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER * Additional information is available in the Quick Start Guide, chapter “EcoStruxure™ Automation Expert Platform Installation”.

    https://www.se.com/ww/en/product-range/62129-modicon-m241-micro-plc/#software-and-firmware
  • BehobenModicon Controllers M251cisa_csaf_ot

    Versions 5.3.12.48 of Modicon Controllers M251 include a fix for this vulnerability and can be downloaded here: M251:https://www.se.com/ww/en/product-range/62130-modicon-m251-micro-plc-with-dual-channel-comm/#software-and-firmware * Use the Controller Assistant feature of EcoStruxure™ Automation Expert - Motion V24.1 or EcoStruxure™ Machine Expert V2.3 to update the M241/M251 firmware and perform a reboot. * EcoStruxure™ Automation Expert - Motion V24.1 and EcoStruxure™ Machine Expert V2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER * Additional information is available in the Quick Start Guide, chapter “EcoStruxure™ Automation Expert Platform Installation”.

    https://www.se.com/ww/en/product-range/62130-modicon-m251-micro-plc-with-dual-channel-comm/#software-and-firmware
  • BehobenModicon Controllers M258cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • MitigationModicon Controllers LMC058cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp

    https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242
  • MitigationModicon Controllers M241cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp

    https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242
  • MitigationModicon Controllers M251cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp

    https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242
  • MitigationModicon Controllers M258cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp

    https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.7
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.6–8.7

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · cybersecurity@se.comAusnutzbarkeit 3.9 · Auswirkung 3.6
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.06.6mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (22)

Betroffene Produkte und Versionsbereiche.

20 von 22 angezeigt
06

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-25-140-08Schneider Electric Modicon Controllers (Update B)2025-05-13icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its Modicon Controllers M241 / M251 / M258 / LMC058 products. The Modicon Controllers M241/M251/M258 https://www.se.com/ww/en/product-category/3900-plc-pac-and-dedicated-controllers/ and Modicon LMC058 https://www.se.com/ww/en/product-range/7744-modicon-lmc058/ products are Programmable Logic Controllers for performance-demanding applications. Failure to apply remediation/mitigations provided below may risk an unauthenticated read of arbitrary files which could result in loss of confidential data stored on the controller. July 2025 Update: A remediation is now available within EcoStruxure™ Machine Expert v2.3 used to update the Modicon Controlers firmware.

07

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2025-05-14geändert 2026-06-17
09

Referenzen (5)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan