Schneider Electric Modicon Controllers (Update B)
Schneider Electric is aware of a vulnerability in its Modicon Controllers M241 / M251 / M258 / LMC058 products. The Modicon Controllers M241/M251/M258 https://www.se.com/ww/en/product-category/3900-plc-pac-and-dedicated-controllers/ and Modicon LMC058 https://www.se.com/ww/en/product-range/7744-modicon-lmc058/ products are Programmable Logic Controllers for performance-demanding applications. Failure to apply remediation/mitigations provided below may risk an unauthenticated read of arbitrary files which could result in loss of confidential data stored on the controller. July 2025 Update: A remediation is now available within EcoStruxure™ Machine Expert v2.3 used to update the Modicon Controlers firmware.
beschreibt (1)
Zugehörige CVEs.
| ID | Schweregrad | ausnutzbar | ||
|---|---|---|---|---|
| CVE-2025-2875US | — | — | ||
CWE-610: Externally Controlled Reference to a Resource in Another Sphere vulnerability exists that could
cause a loss of confidentiality when an unauthenticated attacker manipulate… | ||||
Referenzen
Externe Belege — Patches, Meldungen, Analysen.
- Modicon Controllers M241/M251/M258/LMC058 - SEVD-2025-133-01 PDF Versionself
- Modicon Controllers M241/M251/M258/LMC058 - SEVD-2025-133-01 CSAF Versionself
- ICS Advisory ICSA-25-140-08 JSONself
- ICS Advisory ICSA-25-140-08 - Web Versionself
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
- Recommended Practicesexternal
Behebungen (8)
- MitigationModicon Controllers LMC058
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp
https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242 - MitigationModicon Controllers M241
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp
https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242 - MitigationModicon Controllers M251
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp
https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242 - MitigationModicon Controllers M258
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. • Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. • Deactivate the Webserver after use when not needed. • Use encrypted communication links when available. • Setup network segmentation and implement a firewall to block all unauthorized access to ports 80/HTTP and 443/HTTPS. • Use VPN (Virtual Private Networks) tunnels if remote access is required. • The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific hardening guidelines. To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/en/work/support/cybersecurity/securitynotifications.jsp
https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=EIO0000004242.00.pdf&p_Doc_Ref=EIO0000004242 - BehobenModicon Controllers LMC058
Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.
https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware - BehobenModicon Controllers M241
Versions 5.3.12.48 of Modicon Controllers M241 include a fix for this vulnerability and can be downloaded here: M241:https://www.se.com/ww/en/product-range/62129-modicon-m241-micro-plc/#software-and-firmware * Use the Controller Assistant feature of EcoStruxure™ Automation Expert - Motion V24.1 or EcoStruxure™ Machine Expert V2.3 to update the M241/M251 firmware and perform a reboot. * EcoStruxure™ Automation Expert - Motion V24.1 and EcoStruxure™ Machine Expert V2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER * Additional information is available in the Quick Start Guide, chapter “EcoStruxure™ Automation Expert Platform Installation”.
https://www.se.com/ww/en/product-range/62129-modicon-m241-micro-plc/#software-and-firmware - BehobenModicon Controllers M251
Versions 5.3.12.48 of Modicon Controllers M251 include a fix for this vulnerability and can be downloaded here: M251:https://www.se.com/ww/en/product-range/62130-modicon-m251-micro-plc-with-dual-channel-comm/#software-and-firmware * Use the Controller Assistant feature of EcoStruxure™ Automation Expert - Motion V24.1 or EcoStruxure™ Machine Expert V2.3 to update the M241/M251 firmware and perform a reboot. * EcoStruxure™ Automation Expert - Motion V24.1 and EcoStruxure™ Machine Expert V2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER * Additional information is available in the Quick Start Guide, chapter “EcoStruxure™ Automation Expert Platform Installation”.
https://www.se.com/ww/en/product-range/62130-modicon-m251-micro-plc-with-dual-channel-comm/#software-and-firmware - BehobenModicon Controllers M258
Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.
https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan