CVE-2024-54015

highPriorität · verfolgen · 0OT-Risiko · erhöhtEPSS 0.006 · 48. PerzentilDEEUNLRUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.58% (48th) EPSS
CVSS 7.5 · high
Is it mine?
249 products
Prüfe deine Angriffsfläche
Who says so?
7 sources
cnnvd · enisa_euvd · fstec_bdu · cert_bund

EPSS · bewertet 2026-10-26

A vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V9.90), SIPROTEC 5 6MD85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 6MD86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 6MD89 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 6MD89 (CP300) V9.6x (All versions < V9.68), SIPROTEC 5 6MU85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7KE85 (CP300) (All versions >= V8.80 < V10.0), SIPROTEC 5 7SA82 (CP150) (All versions < V9.90), SIPROTEC 5 7SA86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SA87 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SD82 (CP150) (All versions < V9.90), SIPROTEC 5 7SD86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SD87 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.90), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.90), SIPROTEC 5 7SJ85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SJ86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SK82 (CP150) (All versions < V9.90), SIPROTEC 5 7SK85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SL82 (CP150) (All versions < V9.90), SIPROTEC 5 7SL86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SL87 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SS85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7ST85 (CP300) (All versions >= V8.80 < V10.0), SIPROTEC 5 7ST85 (CP300) V9.6x (All versions < V9.68), SIPROTEC 5 7ST86 (CP300) (All versions < V10.0), SIPROTEC 5 7ST86 (CP300) V9.8x (All versions < V9.83), SIPROTEC 5 7SX82 (CP150) (All versions < V9.90), SIPROTEC 5 7SX85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7SY82 (CP150) (All versions < V9.90), SIPROTEC 5 7UM85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7UT82 (CP150) (All versions < V9.90), SIPROTEC 5 7UT85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7UT86 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7UT87 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7VE85 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7VK87 (CP300) (All versions >= V8.80 < V9.90), SIPROTEC 5 7VU85 (CP300) (All versions < V9.90), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.2) (All versions < V9.90), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.2) V9.6 (All versions < V9.68), SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.2) V9.8 (All versions < V9.83), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 2) (All versions < V9.90), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 2) V9.6 (All versions < V9.68), SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 2) V9.8 (All versions < V9.83), SIPROTEC 5 Communication Module ETH-BD-2FO (All versions >= V8.80 < V9.90), SIPROTEC 5 Communication Module ETH-BD-2FO V9.6 (All versions < V9.68), SIPROTEC 5 Communication Module ETH-BD-2FO V9.8 (All versions < V9.83), SIPROTEC 5 Compact 7SX800 (CP050) (All versions >= V9.50 < V9.90). Affected devices do not properly validate SNMP GET requests. This could allow an unauthenticated, remote attacker to retrieve sensitive information of the affected devices with SNMPv2 GET requests using default credentials.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

8.7
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 6.6–8.7

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · NCSC-NL NL
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · productcert@siemens.com DEAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · Siemens ProductCERT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:Nsecondary · CISA US
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.06.6mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (249)

Betroffene Produkte und Versionsbereiche.

06

Advisories (4)

Hersteller- und Ökosystem-Meldungen dazu.

  • NCSC-2025-0061Kwetsbaarheden verholpen in Siemens productenNL2025-02-14csaf · ncsc_nlNL

    Siemens heeft kwetsbaarheden verholpen in diverse producten als APOGEE, Opcenter, RUGGEDCOM, SCALANCE, SIMATIC, SIPROTEC en Teamcenter.

  • SSA-767615SSA-767615: Information Disclosure Vulnerability in SIPROTEC 5 Devices2025-02-11csaf · siemens_psirtDE

    An information disclosure vulnerability in SIPROTEC 5 devices could allow an unauthenticated, remote attacker to retrieve sensitive information of the device. Siemens has released new versions for the affected products and recommends to update to the latest versions.

  • WID-SEC-W-2025-0313Siemens SIPROTEC: Mehrere SchwachstellenDeutsch2025-02-10csaf · cert_bundDE

    Ein Angreifer mit physischem Zugriff kann mehrere Schwachstellen in Siemens SIPROTEC ausnutzen, um Sicherheitsvorkehrungen zu umgehen oder Informationen auszuspähen.

  • ICSA-25-044-05Siemens SIPROTEC 5 Devices2025-02-11icsa · cisa_csaf_otUS

    An information disclosure vulnerability in SIPROTEC 5 devices could allow an unauthenticated, remote attacker to retrieve sensitive information of the device. Siemens has released new versions for the affected products and recommends to update to the latest versions.

07

auch bekannt als (5)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

09

Referenzen (4)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan