CVE-2024-11737

criticalPriorität · verfolgen · 0EPSS 0.006 · 50. PerzentilEUNLRUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.64% (50th) EPSS
CVSS 9.8 · critical
Is it mine?
24 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-23

CWE-20: Improper Input Validation vulnerability exists that could lead to a denial of service and a loss of confidentiality, integrity of the controller when an unauthenticated crafted Modbus packet is sent to the device.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenModicon Controllers LMC058cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • BehobenModicon Controllers M241cisa_csaf_ot

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • BehobenModicon Controllers M251cisa_csaf_ot

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • BehobenModicon Controllers M258cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • MitigationModicon Controllers LMC058cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M241cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M251cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M258cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 8.1–9.8

v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · cybersecurity@se.comAusnutzbarkeit 3.9 · Auswirkung 5.9
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · NCSC-NL NL
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.1highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: totalcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (24)

Betroffene Produkte und Versionsbereiche.

20 von 24 angezeigt
06

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • NCSC-2024-0489Kwetsbaarheid verholpen in Schneider Electric ModiconNL2024-12-13csaf · ncsc_nlNL

    Schneider Electric heeft een kwetsbaarheid verholpen in apparaten die het Modbus-protocol gebruiken.

  • ICSA-24-352-04Schneider Electric Modicon2024-12-10icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its Modicon M241 / M251 / M258 https://www.se.com/ww/en/product-category/3900-plc-pac-and-dedicated-controllers/ and Modicon LMC058 https://www.se.com/ww/en/product-range/7744-modicon-lmc058/ products. The Modicon M241/M251/M258/LMC058 products are Programmable Logic Controllers for performance-demanding applications. Failure to apply the Fix provided below may risk a denial of service and partial loss of Integrity of the controller, which could result in disruption operations. October 2025 Update: A remediation is now available for Modicon M258 / LMC058

07

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2024-12-11geändert 2026-06-17
09

Referenzen (3)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan