ICSA-24-352-04

icsaUScisa_csaf_ot

Schneider Electric Modicon

Advisory ansehen veröffentlicht 2024-12-10

Schneider Electric is aware of a vulnerability in its Modicon M241 / M251 / M258 https://www.se.com/ww/en/product-category/3900-plc-pac-and-dedicated-controllers/ and Modicon LMC058 https://www.se.com/ww/en/product-range/7744-modicon-lmc058/ products. The Modicon M241/M251/M258/LMC058 products are Programmable Logic Controllers for performance-demanding applications. Failure to apply the Fix provided below may risk a denial of service and partial loss of Integrity of the controller, which could result in disruption operations. October 2025 Update: A remediation is now available for Modicon M258 / LMC058

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2024-11737US——
CWE-20: Improper Input Validation vulnerability exists that could lead to a denial of service and a loss of confidentiality, integrity of the controller when an unauthenticated cra…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (8)

  • MitigationModicon Controllers LMC058

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M241

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M251

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M258

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • BehobenModicon Controllers LMC058

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • BehobenModicon Controllers M241

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • BehobenModicon Controllers M251

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • BehobenModicon Controllers M258

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware