CVE-2022-30315

criticalPriorität · verfolgen · 39OT-Risiko · erhöhtEPSS 0.010 · 62. PerzentilEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.99% (62nd) EPSS
CVSS 9.8 · critical
Is it mine?
6 products
Prüfe deine Angriffsfläche
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · bewertet 2026-10-28

Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • BehobenSafety Managercisa_csaf_ot

    (CVE-2022-30315) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.

  • MitigationSafety Managercisa_csaf_ot

    (CVE-2022-30315) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

9.8
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · high–critical · 7.5–9.8

v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 5.9
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:Nsecondary · CISA US
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

04

betroffene Produkte (6)

Betroffene Produkte und Versionsbereiche.

05

Advisories (1)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-22-207-02Honeywell Safety Manager2022-07-26icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.

06

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

07

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2022-07-28geändert 2026-06-17
09

Referenzen (11)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan