ICSA-22-207-02

icsaUScisa_csaf_ot

Honeywell Safety Manager

Advisory ansehen veröffentlicht 2022-07-26

Successful exploitation of these vulnerabilities could allow for configuration and firmware manipulation or remote code execution.

01

beschreibt (4)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2022-30316USmedium6.8OT erhöht—
Honeywell Experion PKS Safety Manager 5.02 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0054, there is a Honeywell Experion PKS Safety Manager unauthe…
CVE-2022-30315UScritical9.8OT erhöht—
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion…
CVE-2022-30314USmedium4.6OT erhöht—
Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. T…
CVE-2022-30313UShigh7.5OT erhöht—
Honeywell Experion PKS Safety Manager through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0051, there is a Honeywell Experion PKS Safety M…
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (8)

  • MitigationSafety Manager

    (CVE-2022-30313) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.

  • MitigationSafety Manager

    (CVE-2022-30314) Customers should isolate process control networks following our security best practices.

  • MitigationSafety Manager

    (CVE-2022-30315) Safety builder should reside on a station with restrictive access controls. Network controls should be in place to limit the nodes permitted to communicate the builder protocol to the safety manager.

  • MitigationSafety Manager

    Honeywell has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • BehobenSafety Manager

    (CVE-2022-30313) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.

  • BehobenSafety Manager

    (CVE-2022-30314) Safety Manager R160.1 and later releases include a remediation for this item. R160.1 was introduced in October 2014. Users are advised to operate on the latest release and point release.

    https://process.honeywell.com/us/en/products/control-and-supervisory-systems/safety-systems/safety-manager
  • BehobenSafety Manager

    (CVE-2022-30315) Safety Manager and FSC use a key switch control to prevent users from downloading unauthorized safety logic. When the key switch is in the locked state, users cannot download any logic whatsoever.

  • BehobenSafety Manager

    (CVE-2022-30316) The Safety Manager key switch prevents unauthorized firmware from being installed. Users are advised to monitor the key switch position.