Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

01

Behebungen

Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.

Ein Hersteller-Fix ist verfügbar.

  • Behoben SYS600cisa_csaf_ot

    For SYS600: 10.x update to at least SYS600 version 10.4.

  • BehobenGateway Station (GWS)cisa_csaf_ot

    Avoid directly connecting control systems to the internet

  • Mitigation SYS600cisa_csaf_ot

    Do not enable ICCP if it is not used.

02

cvss

Technischer Schweregrad, 0–10. Eine Zeile je Quelle.

7.5
010

Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.3–7.5

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USAusnutzbarkeit 3.9 · Auswirkung 3.6
v3.05.3mediumCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.15.3mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · ENISA EU
v3.15.3mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Lsecondary · cybersecurity@hitachienergy.comAusnutzbarkeit 3.9 · Auswirkung 1.4
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

SSVC

Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

schwächen

Die CWE-Schwächeklassen, zu denen dies gehört.

05

betroffene Produkte (16)

Betroffene Produkte und Versionsbereiche.

06

Advisories (2)

Hersteller- und Ökosystem-Meldungen dazu.

  • ICSA-22-272-01Hitachi Energy MicroSCADA Pro X SYS6002022-09-29icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability could cause SYS600 fail to start or an unauthorized actor to run scripts, and could cause a denial-of-service condition.

  • ICSA-23-059-02Hitachi Energy Gateway Station2023-03-06icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities could cause part of GWS fail to start, allow unauthorized actors to run scripts, and/or cause a denial-of-service.

07

auch bekannt als (4)

Weitere Namen und Kennungen dieser Entität.

08

quellen

Welche Quellen diesen Datensatz belegen und wann.

veröffentlicht 2022-09-14geändert 2026-06-17
10

Referenzen (5)

Externe Belege — Patches, Meldungen, Analysen.

scry

Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan