CVE-2022-29492
highPriorität · verfolgen · 30EPSS 0.007 · 55. PerzentilEURUUSEPSS · bewertet 2026-10-27
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- Behoben SYS600cisa_csaf_ot
For SYS600: 10.x update to at least SYS600 version 10.4.
- BehobenGateway Station (GWS)cisa_csaf_ot
Avoid directly connecting control systems to the internet
- Mitigation SYS600cisa_csaf_ot
Do not enable ICCP if it is not used.
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 5.3–7.5
SSVC
Eine Handlungsentscheidung — aus Ausnutzung und Auswirkung.
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (16)
Betroffene Produkte und Versionsbereiche.
- hitachienergy microscada x sys6009.0 → 10.4nvdUScpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:*
Advisories (2)
Hersteller- und Ökosystem-Meldungen dazu.
- ICSA-22-272-01Hitachi Energy MicroSCADA Pro X SYS6002022-09-29icsa · cisa_csaf_otUS
Successful exploitation of this vulnerability could cause SYS600 fail to start or an unauthorized actor to run scripts, and could cause a denial-of-service condition.
- ICSA-23-059-02Hitachi Energy Gateway Station2023-03-06icsa · cisa_csaf_otUS
Successful exploitation of these vulnerabilities could cause part of GWS fail to start, allow unauthorized actors to run scripts, and/or cause a denial-of-service.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (5)
Externe Belege — Patches, Meldungen, Analysen.
- https://cxsecurity.com/cveshow/CVE-2022-29492/cnnvd
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launchcnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-272-01cnnvd
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launchenisa_euvd
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=LaunchVendor Advisorynvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan