CVE-2019-10923
mediumPriorität · verfolgen · 20EPSS 0.014 · 72. PerzentilDEEURUUSEPSS · bewertet 2026-10-23
An attacker with network access to an affected product may cause a denial of service condition by breaking the real-time synchronization (IRT) of the affected installation.
Behebungen
Hersteller-Fix, Mitigation oder Workaround, wie von den Quellen veröffentlicht.
Ein Hersteller-Fix ist verfügbar.
- Behoben SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)siemens_psirt
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)siemens_psirt
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)siemens_psirt
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)siemens_psirt
Update to V7.0.3 or later version
- BehobenDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controllersiemens_psirt
Update to V4.1.1 Patch 05 or later version
https://support.industry.siemens.com/cs/ww/en/view/109755160/ - BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200siemens_psirt
Update to V4.5.0 Patch 01 or later version
https://support.industry.siemens.com/cs/ww/en/view/109760397/ - BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200Psiemens_psirt
Update to V4.5.0 or later version
https://support.industry.siemens.com/cs/ww/en/view/109750012/ - BehobenSCALANCE X-200IRT family (incl. SIPLUS NET variants)siemens_psirt
Update to V5.4.2
https://support.industry.siemens.com/cs/ww/en/view/109763309 - BehobenSIMATIC CP 1604 (6GK1160-4AA01)siemens_psirt
Update to V2.8 or later version
https://support.industry.siemens.com/cs/ww/en/view/109762689/ - BehobenSIMATIC CP 1616 (6GK1161-6AA02)siemens_psirt
Update to V2.8
https://support.industry.siemens.com/cs/ww/en/view/109762689/ - BehobenSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47353723/ - BehobenSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354354/ - BehobenSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354502/ - BehobenSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354578/ - BehobenSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/62612377/ - BehobenSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/51466769/ - BehobenSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40360647/ - BehobenSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40944925/ - BehobenSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85049260/ - BehobenSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40362228/ - BehobenSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40945128/ - BehobenSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85059804/ - BehobenSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85063017/ - BehobenSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/44442927/ - BehobenSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/44443101/ - BehobenSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)siemens_psirt
Update to V7.0.3 or later version
- BehobenSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)siemens_psirt
Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates
https://support.industry.siemens.com/cs/ww/en/view/109765109/ - BehobenSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)siemens_psirt
Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates
https://support.industry.siemens.com/cs/ww/en/view/109765109/ - BehobenSINAMICS DCMsiemens_psirt
Update to V1.5 HF1 or later version
https://support.industry.siemens.com/cs/us/en/view/44029688 - BehobenSINAMICS DCPsiemens_psirt
Update to V1.3
https://support.industry.siemens.com/cs/ww/de/view/109773826 - BehobenSINAMICS G110M V4.7 Control Unitsiemens_psirt
Update to V4.7 SP10 HF5
https://support.industry.siemens.com/cs/us/en/view/109756820 - BehobenSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)siemens_psirt
Update to V4.7 SP10 HF5
https://support.industry.siemens.com/cs/us/en/view/109756820 - BehobenSINAMICS G130siemens_psirt
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS G150siemens_psirt
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS GH150 V4.7 Control Unitsiemens_psirt
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS GL150 V4.7 Control Unitsiemens_psirt
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS GM150 V4.7 Control Unitsiemens_psirt
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)siemens_psirt
Update to V4.7 HF34 or upgrade to V5.2 HF2
https://support.industry.siemens.com/cs/us/en/view/92522512 - BehobenSINAMICS S150siemens_psirt
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS SL150 V4.7 Control Unitsiemens_psirt
Update to V4.7 HF33 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINUMERIK 828Dsiemens_psirt
Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINUMERIK 840D slsiemens_psirt
Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47353723/ - BehobenSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354354/ - BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)siemens_psirt
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)siemens_psirt
Update to V4.1.0 or later version
- BehobenSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)siemens_psirt
Update to V3.3.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/51466769/ - BehobenSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40360647/ - BehobenSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40944925/ - BehobenSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40362228/ - BehobenSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)siemens_psirt
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40945128/ - BehobenSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)siemens_psirt
Update to V7.0.3 or later version
- BehobenSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)siemens_psirt
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- Behoben SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- BehobenDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controllercisa_csaf_ot
Update to V4.1.1 Patch 05 or later version
https://support.industry.siemens.com/cs/ww/en/view/109755160/ - BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200cisa_csaf_ot
Update to V4.5.0 Patch 01 or later version
https://support.industry.siemens.com/cs/ww/en/view/109760397/ - BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200Pcisa_csaf_ot
Update to V4.5.0 or later version
https://support.industry.siemens.com/cs/ww/en/view/109750012/ - BehobenSCALANCE X-200IRT family (incl. SIPLUS NET variants)cisa_csaf_ot
Update to V5.4.2
https://support.industry.siemens.com/cs/ww/en/view/109763309 - BehobenSIMATIC CP 1604 (6GK1160-4AA01)cisa_csaf_ot
Update to V2.8 or later version
https://support.industry.siemens.com/cs/ww/en/view/109762689/ - BehobenSIMATIC CP 1616 (6GK1161-6AA02)cisa_csaf_ot
Update to V2.8
https://support.industry.siemens.com/cs/ww/en/view/109762689/ - BehobenSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47353723/ - BehobenSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354354/ - BehobenSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354502/ - BehobenSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354578/ - BehobenSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/62612377/ - BehobenSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/51466769/ - BehobenSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40360647/ - BehobenSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40944925/ - BehobenSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85049260/ - BehobenSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40362228/ - BehobenSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40945128/ - BehobenSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85059804/ - BehobenSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/85063017/ - BehobenSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/44442927/ - BehobenSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/44443101/ - BehobenSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- BehobenSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)cisa_csaf_ot
Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates
https://support.industry.siemens.com/cs/ww/en/view/109765109/ - BehobenSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)cisa_csaf_ot
Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates
https://support.industry.siemens.com/cs/ww/en/view/109765109/ - BehobenSINAMICS DCMcisa_csaf_ot
Update to V1.5 HF1 or later version
https://support.industry.siemens.com/cs/us/en/view/44029688 - BehobenSINAMICS DCPcisa_csaf_ot
Update to V1.3
https://support.industry.siemens.com/cs/ww/de/view/109773826 - BehobenSINAMICS G110M V4.7 Control Unitcisa_csaf_ot
Update to V4.7 SP10 HF5
https://support.industry.siemens.com/cs/us/en/view/109756820 - BehobenSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)cisa_csaf_ot
Update to V4.7 SP10 HF5
https://support.industry.siemens.com/cs/us/en/view/109756820 - BehobenSINAMICS G130cisa_csaf_ot
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS G150cisa_csaf_ot
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS GH150 V4.7 Control Unitcisa_csaf_ot
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS GL150 V4.7 Control Unitcisa_csaf_ot
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS GM150 V4.7 Control Unitcisa_csaf_ot
Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)cisa_csaf_ot
Update to V4.7 HF34 or upgrade to V5.2 HF2
https://support.industry.siemens.com/cs/us/en/view/92522512 - BehobenSINAMICS S150cisa_csaf_ot
Update to V4.7 HF29 or later version
https://support.industry.siemens.com/cs/ww/en/view/103433117/ - BehobenSINAMICS SL150 V4.7 Control Unitcisa_csaf_ot
Update to V4.7 HF33 The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINUMERIK 828Dcisa_csaf_ot
Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSINUMERIK 840D slcisa_csaf_ot
Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.
- BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47353723/ - BehobenSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/47354354/ - BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)cisa_csaf_ot
Update to V4.2.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)cisa_csaf_ot
Update to V4.1.0 or later version
- BehobenSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)cisa_csaf_ot
Update to V3.3.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/51466769/ - BehobenSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40360647/ - BehobenSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40944925/ - BehobenSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40362228/ - BehobenSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)cisa_csaf_ot
Update to V3.2.17 or later version
https://support.industry.siemens.com/cs/ww/en/view/40945128/ - BehobenSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- BehobenSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)cisa_csaf_ot
Update to V7.0.3 or later version
- Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controllersiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200Psiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSCALANCE X-200IRT family (incl. SIPLUS NET variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC CP 1604 (6GK1160-4AA01)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC CP 1616 (6GK1161-6AA02)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200M (incl. SIPLUS variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200S (incl. SIPLUS variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMOTIONsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS DCMsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS DCPsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G110M V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G130siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G150siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GH150 V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GL150 V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GM150 V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S110 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S150siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS SL150 V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS SM120 V4.7 Control Unitsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINUMERIK 828Dsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINUMERIK 840D slsiemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)siemens_psirt
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controllercisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200Pcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSCALANCE X-200IRT family (incl. SIPLUS NET variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC CP 1604 (6GK1160-4AA01)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC CP 1616 (6GK1161-6AA02)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200M (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200S (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIMOTIONcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS DCMcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS DCPcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G110M V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G130cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS G150cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GH150 V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GL150 V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS GM150 V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S110 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS S150cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS SL150 V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINAMICS SM120 V4.7 Control Unitcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINUMERIK 828Dcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSINUMERIK 840D slcisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)cisa_csaf_ot
Disable SNMP in Versions 1 and 2c, if supported by the product.
- Kein Fix geplantSIMATIC ET 200M (incl. SIPLUS variants)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200S (incl. SIPLUS variants)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)siemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMOTIONsiemens_psirt
Currently no fix is planned
- Kein Fix geplantSINAMICS S110 Control Unitsiemens_psirt
Currently no fix is planned
- Kein Fix geplantSINAMICS SM120 V4.7 Control Unitsiemens_psirt
Currently no fix is planned
- Kein Fix geplantSIMATIC ET 200M (incl. SIPLUS variants)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200S (incl. SIPLUS variants)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)cisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSIMOTIONcisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSINAMICS S110 Control Unitcisa_csaf_ot
Currently no fix is planned
- Kein Fix geplantSINAMICS SM120 V4.7 Control Unitcisa_csaf_ot
Currently no fix is planned
cvss
Technischer Schweregrad, 0–10. Eine Zeile je Quelle.
Basiswert 0–10 · höher = schwerwiegender · Vektor überfahren zum Auflösen⚠ Quellen uneinig · medium–high · 4.3–7.5
schwächen
Die CWE-Schwächeklassen, zu denen dies gehört.
betroffene Produkte (443)
Betroffene Produkte und Versionsbereiche.
Advisories (3)
Hersteller- und Ökosystem-Meldungen dazu.
- SSA-349422SSA-349422: Denial of Service Vulnerability in Industrial Real-Time (IRT) Devices2019-10-08csaf · siemens_psirtDE
A vulnerability in the affected products could allow an unauthorized attacker with network access to perform a denial-of-service attack resulting in loss of real-time synchronization. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where fixes are not, or not yet available.
- WID-SEC-W-2023-0898Siemens SIMATIC S7: Schwachstelle ermöglicht Denial of ServiceDeutsch2023-04-10csaf · cert_bundDE
Ein entfernter, anonymer Angreifer kann eine Schwachstelle in Siemens SIMATIC S7 ausnutzen, um einen Denial of Service Angriff durchzuführen.
- ICSA-19-283-01Siemens Industrial Real-Time (IRT) Devices2019-10-08icsa · cisa_csaf_otUS
A vulnerability in the affected products could allow an unauthorized attacker with network access to perform a denial-of-service attack resulting in loss of real-time synchronization. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where fixes are not, or not yet available.
auch bekannt als (4)
Weitere Namen und Kennungen dieser Entität.
quellen
Welche Quellen diesen Datensatz belegen und wann.
Referenzen (12)
Externe Belege — Patches, Meldungen, Analysen.
- https://cert-portal.siemens.com/productcert/html/ssa-349422.htmlcnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-349422.pdfcnnvd
- https://nvd.nist.gov/vuln/detail/CVE-2019-10923cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-19-283-01cnnvd
- https://vigilance.fr/vulnerability/SIMATIC-denial-of-service-via-IRT-30559cnnvd
- https://www.auscert.org.au/bulletins/ESB-2019.3812.2/cnnvd
- https://www.auscert.org.au/bulletins/ESB-2019.3812/cnnvd
- https://www.us-cert.gov/ics/advisories/icsa-19-283-01cnnvd
Angreifer nutzen Schwachstellen wie diese gegen im Internet exponierte Dienste aus. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.
Kostenloser Scan