ICSA-19-283-01

icsaUScisa_csaf_ot

Siemens Industrial Real-Time (IRT) Devices

Advisory ansehen veröffentlicht 2019-10-08

A vulnerability in the affected products could allow an unauthorized attacker with network access to perform a denial-of-service attack resulting in loss of real-time synchronization. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens recommends specific countermeasures for products where fixes are not, or not yet available.

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2019-10923USmedium5.0—
An attacker with network access to an affected product may cause a denial of service condition by breaking the real-time synchronization (IRT) of the affected installation.
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (180)

  • Mitigation SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • Mitigation SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • Mitigation SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • Mitigation SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSCALANCE X-200IRT family (incl. SIPLUS NET variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC CP 1604 (6GK1160-4AA01)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC CP 1616 (6GK1161-6AA02)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200M (incl. SIPLUS variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200S (incl. SIPLUS variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIMOTION

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS DCM

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS DCP

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS G110M V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS G130

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS G150

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS GH150 V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS GL150 V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS GM150 V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS S110 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS S150

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS SL150 V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINAMICS SM120 V4.7 Control Unit

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINUMERIK 828D

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSINUMERIK 840D sl

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • MitigationSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Disable SNMP in Versions 1 and 2c, if supported by the product.

  • Kein Fix geplantSIMATIC ET 200M (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200S (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMOTION

    Currently no fix is planned

  • Kein Fix geplantSINAMICS S110 Control Unit

    Currently no fix is planned

  • Kein Fix geplantSINAMICS SM120 V4.7 Control Unit

    Currently no fix is planned

  • Behoben SIMATIC S7-400 CPU 414-3 PN/DP V7 (6ES7414-3EM07-0AB0)

    Update to V7.0.3 or later version

  • Behoben SIMATIC S7-400 CPU 414F-3 PN/DP V7 (6ES7414-3FM07-0AB0)

    Update to V7.0.3 or later version

  • Behoben SIMATIC S7-400 CPU 416-3 PN/DP V7 (6ES7416-3ES07-0AB0)

    Update to V7.0.3 or later version

  • Behoben SIMATIC S7-400 CPU 416F-3 PN/DP V7 (6ES7416-3FS07-0AB0)

    Update to V7.0.3 or later version

  • BehobenDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Update to V4.1.1 Patch 05 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109755160/
  • BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Update to V4.5.0 Patch 01 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109760397/
  • BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Update to V4.5.0 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109750012/
  • BehobenSCALANCE X-200IRT family (incl. SIPLUS NET variants)

    Update to V5.4.2

    https://support.industry.siemens.com/cs/ww/en/view/109763309
  • BehobenSIMATIC CP 1604 (6GK1160-4AA01)

    Update to V2.8 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109762689/
  • BehobenSIMATIC CP 1616 (6GK1161-6AA02)

    Update to V2.8

    https://support.industry.siemens.com/cs/ww/en/view/109762689/
  • BehobenSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Update to V4.2.0 or later version

  • BehobenSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Update to V4.1.0 or later version

  • BehobenSIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • BehobenSIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • BehobenSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Update to V4.2.0 or later version

  • BehobenSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Update to V4.1.0 or later version

  • BehobenSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Update to V4.1.0 or later version

  • BehobenSIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354502/
  • BehobenSIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354578/
  • BehobenSIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/62612377/
  • BehobenSIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • BehobenSIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • BehobenSIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • BehobenSIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85049260/
  • BehobenSIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • BehobenSIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/
  • BehobenSIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85059804/
  • BehobenSIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/85063017/
  • BehobenSIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44442927/
  • BehobenSIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/44443101/
  • BehobenSIMATIC S7-400 CPU 412-2 PN V7 (6ES7412-2EK07-0AB0)

    Update to V7.0.3 or later version

  • BehobenSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • BehobenSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • BehobenSINAMICS DCM

    Update to V1.5 HF1 or later version

    https://support.industry.siemens.com/cs/us/en/view/44029688
  • BehobenSINAMICS DCP

    Update to V1.3

    https://support.industry.siemens.com/cs/ww/de/view/109773826
  • BehobenSINAMICS G110M V4.7 Control Unit

    Update to V4.7 SP10 HF5

    https://support.industry.siemens.com/cs/us/en/view/109756820
  • BehobenSINAMICS G120 V4.7 Control Unit (incl. SIPLUS variants)

    Update to V4.7 SP10 HF5

    https://support.industry.siemens.com/cs/us/en/view/109756820
  • BehobenSINAMICS G130

    Update to V4.7 HF29 or later version

    https://support.industry.siemens.com/cs/ww/en/view/103433117/
  • BehobenSINAMICS G150

    Update to V4.7 HF29 or later version

    https://support.industry.siemens.com/cs/ww/en/view/103433117/
  • BehobenSINAMICS GH150 V4.7 Control Unit

    Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSINAMICS GL150 V4.7 Control Unit

    Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSINAMICS GM150 V4.7 Control Unit

    Update to V4.8 SP2 HF9 The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSINAMICS S120 V4.7 Control Unit and CBE20 (incl. SIPLUS variants)

    Update to V4.7 HF34 or upgrade to V5.2 HF2

    https://support.industry.siemens.com/cs/us/en/view/92522512
  • BehobenSINAMICS S150

    Update to V4.7 HF29 or later version

    https://support.industry.siemens.com/cs/ww/en/view/103433117/
  • BehobenSINAMICS SL150 V4.7 Control Unit

    Update to V4.7 HF33 The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSINUMERIK 828D

    Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSINUMERIK 840D sl

    Update to V4.8 SP5 or later version The update can be obtained from your Siemens representative or via Siemens customer service.

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47353723/
  • BehobenSIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/47354354/
  • BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0)

    Update to V3.3.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/51466769/
  • BehobenSIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40360647/
  • BehobenSIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40944925/
  • BehobenSIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40362228/
  • BehobenSIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0)

    Update to V3.2.17 or later version

    https://support.industry.siemens.com/cs/ww/en/view/40945128/
  • BehobenSIPLUS S7-400 CPU 414-3 PN/DP V7 (6AG1414-3EM07-7AB0)

    Update to V7.0.3 or later version

  • BehobenSIPLUS S7-400 CPU 416-3 PN/DP V7 (6AG1416-3ES07-7AB0)

    Update to V7.0.3 or later version

scry

Advisories wie diese benennen die exponierten Produkte, die Angreifer auf Ihrer Angriffsfläche ins Visier nehmen. Sehen Sie mit einem kostenlosen Passiv-Scan, was exponiert ist.

Kostenloser Scan