ICSA-17-339-01

icsaUScisa_csaf_ot

Siemens Industrial Products (Update S)

Advisory ansehen veröffentlicht 2017-11-23

Several industrial products are affected by a vulnerability that could allow remote attackers to conduct a denial of service attack by sending specially crafted packets to port 161/udp (SNMP). Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.

01

beschreibt (1)

Zugehörige CVEs.

IDSchweregrad ausnutzbar
CVE-2017-12741UShigh7.5—
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
02

Referenzen

Externe Belege — Patches, Meldungen, Analysen.

03

Behebungen (172)

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC Compact Field Unit

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200M (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200MP IM 155-5 PN BA (6ES7155-5AA00-0AA0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN BA (6ES7155-6AR00-0AN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN HS (6ES7155-6AU00-0DN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU01-0BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA01-0BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200S (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-1500 Software Controller

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-200 SMART

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC TDC CP51M1

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC TDC CPU555

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMOCODE pro V PROFINET (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMOTION C

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMOTION D

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMOTION P V4.4 and V4.5

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIMOTION P V5

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS DCM w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS DCP w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G110M w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G130 V4.7 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G130 V4.8 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G150 V4.7 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS G150 V4.8 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S110 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S120 V4.7 w. PN (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S120 V4.8 w. PN (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S120 prior to V4.7 w. PN (incl. SIPLUS variants)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S150 V4.7 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS S150 V4.8 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINAMICS V90 w. PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSINUMERIK 840D sl

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU01-7BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA01-7BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA01-4BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU01-4BN0)

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • MitigationSIRIUS Soft Starter 3RW44 PN

    Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability.

  • Kein Fix geplantSIMATIC ET 200M (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN BA (6ES7155-6AR00-0AN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU00-0BN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN ST (6ES7155-6AU01-0BN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA00-0BN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200SP IM 155-6 PN ST BA (6ES7155-6AA01-0BN0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200pro IM 154-3 PN HF (6ES7154-3AB00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET 200pro IM 154-4 PN HF (6ES7154-4AB10-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200S (incl. SIPLUS variants)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU00-7BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST (6AG1155-6AU01-7BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA00-7BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST BA (6AG1155-6AA01-7BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA00-4BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST BA TX RAIL (6AG2155-6AA01-4BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU00-4BN0)

    Currently no fix is planned

  • Kein Fix geplantSIPLUS ET 200SP IM 155-6 PN ST TX RAIL (6AG2155-6AU01-4BN0)

    Currently no fix is planned

  • Kein Fix verfügbarSIMATIC Compact Field Unit

    Currently no fix is available

  • Kein Fix verfügbarSIRIUS Soft Starter 3RW44 PN

    Currently no fix is available

  • BehobenDevelopment/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller

    Update to V4.1.1 Patch 05

    https://support.industry.siemens.com/cs/ww/en/view/109755160
  • BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200

    Update to V4.5

    https://support.industry.siemens.com/cs/ww/en/view/109755151
  • BehobenDevelopment/Evaluation Kits for PROFINET IO: EK-ERTEC 200P

    Update to V4.5

    https://support.industry.siemens.com/cs/ww/en/view/109750012
  • BehobenSIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0)

    Update to V1.0.2 or later version

  • BehobenSIMATIC ET 200MP IM 155-5 PN BA (6ES7155-5AA00-0AA0)

    Update to V4.0.2 or later version

  • BehobenSIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0)

    Update to V4.2.0 or later version

  • BehobenSIMATIC ET 200MP IM 155-5 PN ST (6ES7155-5AA00-0AB0)

    Update to V4.1.0 or later version

  • BehobenSIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    Update to V1.1.0

    https://support.industry.siemens.com/cs/ww/en/view/109763483
  • BehobenSIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0)

    Update to V4.2.0 or later version

  • BehobenSIMATIC ET 200SP IM 155-6 PN HS (6ES7155-6AU00-0DN0)

    Update to V4.0.1 or later version

  • BehobenSIMATIC PN/PN Coupler (incl. SIPLUS NET variants)

    Update to V4.2.0

    https://support.industry.siemens.com/cs/ww/en/view/109760973
  • BehobenSIMATIC S7-1200 CPU family (incl. SIPLUS variants)

    Update to V4.2.3

    https://support.industry.siemens.com/cs/us/en/view/109741461
  • BehobenSIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Upgrade to V2.0 or newer

    https://support.industry.siemens.com/cs/us/en/ps/13717/dl
  • BehobenSIMATIC S7-1500 Software Controller

    Upgrade to V2.0 or newer

    https://support.industry.siemens.com/cs/us/en/view/109478528
  • BehobenSIMATIC S7-200 SMART

    Update to V2.03.01

    https://support.industry.siemens.com/cs/cn/en/view/109749409
  • BehobenSIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)

    Update to V3.X.16 or later version

    https://support.industry.siemens.com/cs/ww/en/ps/13752/dl
  • BehobenSIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants)

    Update to V6.0.8 or later version

  • BehobenSIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

    Update to V6.0.6 or later version

  • BehobenSIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants)

    Update to V7.0.2 or later version

  • BehobenSIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)

    Update to V8.2.1

    https://support.industry.siemens.com/cs/ww/en/view/109476571
  • BehobenSIMATIC TDC CP51M1

    Update to V1.1.8 or later version

    https://support.industry.siemens.com/cs/ww/en/view/27049282/
  • BehobenSIMATIC TDC CPU555

    Update to V1.1.1 or later version

    https://support.industry.siemens.com/cs/ww/en/view/109740119/
  • BehobenSIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • BehobenSIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0)

    Update to V2010 SP3 or later version and apply BIOS and Microsoft Windows updates

    https://support.industry.siemens.com/cs/ww/en/view/109765109/
  • BehobenSIMOCODE pro V PROFINET (incl. SIPLUS variants)

    Update to V2.1.1

    https://support.industry.siemens.com/cs/ww/en/view/109749989
  • BehobenSIMOTION C

    Update to V5.1 HF1

    https://support.industry.siemens.com/cs/ww/en/view/31263919
  • BehobenSIMOTION D

    Update to V5.1 HF1

    https://support.industry.siemens.com/cs/ww/en/view/31045047
  • BehobenSIMOTION P V4.4 and V4.5

    Update to V4.5 HF5 Please contact your Siemens representative for information on how to obtain the update.

  • BehobenSIMOTION P V5

    Update to V5.1 HF1 Please contact your Siemens representative for information on how to obtain the update.

  • BehobenSINAMICS DCM w. PN

    Update to V1.4 SP1 HF6

    https://support.industry.siemens.com/cs/ww/en/view/44029688
  • BehobenSINAMICS DCP w. PN

    Update to V1.2 HF2

    https://support.industry.siemens.com/cs/ww/en/view/109474935
  • BehobenSINAMICS G110M w. PN

    Update to V4.7 SP9 HF1

    https://support.industry.siemens.com/cs/document/109750507
  • BehobenSINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants)

    Update to V4.7 SP9 HF1

    https://support.industry.siemens.com/cs/document/109750507
  • BehobenSINAMICS G130 V4.7 w. PN

    Update to V4.7 HF29

    https://support.industry.siemens.com/cs/ww/en/view/103433117
  • BehobenSINAMICS G130 V4.8 w. PN

    Update to V4.8 HF4

    https://support.industry.siemens.com/cs/ww/en/view/109742040
  • BehobenSINAMICS G150 V4.7 w. PN

    Update to V4.7 HF29

    https://support.industry.siemens.com/cs/ww/en/view/103433117
  • BehobenSINAMICS G150 V4.8 w. PN

    Update to V4.8 HF4

    https://support.industry.siemens.com/cs/ww/en/view/109742040
  • BehobenSINAMICS S110 w. PN

    Update to V4.4 SP3 HF6

    https://support.industry.siemens.com/cs/document/109474320
  • BehobenSINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants)

    Update to latest version of V5.1 SP1

    https://support.industry.siemens.com/cs/document/109758423
  • BehobenSINAMICS S120 V4.7 w. PN (incl. SIPLUS variants)

    Update to V4.7 HF29

    https://support.industry.siemens.com/cs/ww/en/view/92522512
  • BehobenSINAMICS S120 V4.8 w. PN (incl. SIPLUS variants)

    Update to V4.8 HF5

    https://support.industry.siemens.com/cs/us/en/view/109740193
  • BehobenSINAMICS S120 prior to V4.7 w. PN (incl. SIPLUS variants)

    Update to latest version of V5.1 SP1

    https://support.industry.siemens.com/cs/document/109758423
  • BehobenSINAMICS S150 V4.7 w. PN

    Update to V4.7 HF29

    https://support.industry.siemens.com/cs/ww/en/view/103433117
  • BehobenSINAMICS S150 V4.8 w. PN

    Update to V4.8 HF4

    https://support.industry.siemens.com/cs/ww/en/view/109742040
  • BehobenSINAMICS V90 w. PN

    Update to V1.02

    https://support.industry.siemens.com/cs/document/109746210
  • BehobenSINUMERIK 840D sl

    Update to V4.8 SP3 The update can be obtained from your local service organization.

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN ST (6AG1155-5AA00-7AB0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200MP IM 155-5 PN ST TX RAIL (6AG2155-5AA00-4AB0)

    Update to V4.1.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0)

    Update to V4.2.0 or later version

  • BehobenSIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0)

    Update to V4.2.0 or later version