SSA-111512

csafDEsiemens_psirt

SSA-111512: Client-side Authentication in SIMATIC WinCC OA

view advisory published 2022-06-21

SIMATIC WinCC OA implements client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated. Siemens recommends to enable server-side authentication (SSA) or Kerberos authentication for all WinCC OA projects, as documented in the WinCC OA Security Guideline. In SIMATIC WinCC OA server-side authentication is available since V3.15 (and offered as the default configuration since V3.17). Additional information can be found at: https://cert-portal.siemens.com/productcert/news.html?id=21.

01

describes (1)

Related CVEs.

IDseverity exploitable
CVE-2022-33139UScritical9.8—
A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All versions), SIMATIC WinCC OA V3.16 (All versions in default conf…
02

references

External citations — patches, advisories, analysis.

03

remediations (3)

scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan