ICSA-18-102-02

icsaUScisa_csaf_ot

Rockwell Automation FactoryTalk Activation Manager (Update B)

view advisory published 2018-04-12

Successful exploitation of these vulnerabilities could allow a remote attacker to access sensitive information, rewrite content, or cause a buffer overflow that could result in remote code execution.

01

describes (2)

Related CVEs.

IDseverity exploitable
CVE-2017-13754USmedium5.4Exploit
Cross-site scripting (XSS) vulnerability in the "advanced settings - time server" module in Wibu-Systems CodeMeter before 6.50b allows remote attackers to inject arbitrary web scri…
CVE-2015-8277UScritical9.8Exploit
Multiple buffer overflows in (1) lmgrd and (2) Vendor Daemon in Flexera FlexNet Publisher before 11.13.1.2 Security Update 1 allow remote attackers to execute arbitrary code via a…
02

references

External citations — patches, advisories, analysis.

03

remediations (4)

  • MitigationFactoryTalk Activation Manager

    Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP and UDP and Port 44818/TCP and UDP, using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270 available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1 (Login required).

  • MitigationFactoryTalk Activation Manager

    Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP and UDP and Port 44818/TCP and UDP, using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270 available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1 (Login required).

  • FixedFactoryTalk Activation Manager

    Rockwell Automation recommends users with affected versions of CodeMeter and/or FlexNet Publisher that were installed with FactoryTalk Activation Manager to update Factory Talk Activation Manager to v4.02. If unable to update FactoryTalk Activation Manager to v4.02, update CodeMeter to a compatible version of CodeMeter that is compatible with FactoryTalk Activation Manager.

  • FixedFactoryTalk Activation Manager

    Rockwell Automation recommends users with affected versions of CodeMeter and/or FlexNet Publisher that were installed with FactoryTalk Activation Manager to update Factory Talk Activation Manager to v4.02. If unable to update FactoryTalk Activation Manager to v4.02, update CodeMeter to a compatible version of CodeMeter that is compatible with FactoryTalk Activation Manager.

scry

Advisories like this name the exposed products attackers go after on your perimeter. See what is exposed on your perimeter with a free passive scan.

Free scan