CWE-78 Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could allow unauthorized execution of commands with elevated privileges, impacting system integrity, confidentiality, and availability when a privileged authenticated user interacts with a vulnerable network-exposed service.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedPowerLogic™ P7cisa_csaf_ot
Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability and is available for download here: • Contact Schneider Electric’s Customer Care Center to download this firmware. • Reboot needed: Yes
- MitigationPowerLogic™ P7cisa_csaf_ot
If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Restrict network access to P7 service endpoints (ports 8080 and 3702) • Monitor and alert on anomalous SOAP requests targeting wsApp • Limit administrative access and apply least privilege principles for all users interacting with P7.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.1–8.6
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (7)
Products and version ranges known to be affected.
- schneider-electric powerlogic p7 firmware< 02.004.001.000nvdUScpe:2.3:o:schneider-electric:powerlogic_p7_firmware:*:*:*:*:*:*:*:*
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-26-176-07Schneider Electric PowerLogic P72026-06-09icsa · cisa_csaf_otUS
Schneider Electric is aware of a vulnerability in its PowerLogic™ P7 product. The PowerLogic™ P7 is a protection and control platform designed for complex and advanced electrical network applications. Failure to apply the remediation provided below may risk unauthorized execution of privileged commands or loss of HMI operability and configuration functionality, which could result in loss of control over system operations and disruption of critical services.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (3)
External citations — patches, advisories, analysis.
- https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-160-03&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2026-160-03.pdfcnnvd