CVE-2026-9716

highpriority · track · 30EPSS 0.005 · 40 %ileEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.46% (40th) EPSS
CVSS 7.5 · high
Is it mine?
7 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

CWE-476 NULL Pointer Dereference vulnerability exists that could cause a denial-of-service condition, rendering the device’s HMI and configuration functionality unavailable when malformed requests are received over exposed network interfaces.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedPowerLogic™ P7cisa_csaf_ot

    Version V02.004.001 of PowerLogicTM P7 includes a fix for this vulnerability and is available for download here: • Contact Schneider Electric’s Customer Care Center to download this firmware. • Reboot needed: Yes

  • MitigationPowerLogic™ P7cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: • Restrict network access to P7 service endpoints (ports 8080 and 3702) • Monitor and alert on anomalous SOAP requests targeting wsApp • Limit administrative access and apply least privilege principles for all users interacting with P7.

02

cvss

Technical severity, 0–10. One row per scoring source.

8.7
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.6–8.7

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.06.6mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (7)

Products and version ranges known to be affected.

06

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-26-176-07Schneider Electric PowerLogic P72026-06-09icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its PowerLogic™ P7 product. The PowerLogic™ P7 is a protection and control platform designed for complex and advanced electrical network applications. Failure to apply the remediation provided below may risk unauthorized execution of privileged commands or loss of HMI operability and configuration functionality, which could result in loss of control over system operations and disruption of critical services.

07

also known as (4)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (3)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan