CVE-2026-79625
highpriority · track · 32EPSS 0.002 · 14 %ileDEEPSS · scored 2026-10-27
Affected products do not properly synchronize access to their monitoring functionality. When multiple clients send concurrent requests, this may lead to incorrect reads or writes, or to corruption of internal memory structures. An authenticated remote attacker with monitoring access can exploit this issue to cause incorrect data processing or a denial-of-service condition.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- Fixedcodesys_psirt
Update the following products to version 3.5.22.40. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS Runtime Toolkit * CODESYS Safety SIL2 * CODESYS HMI (SL) * CODESYS Development System 3 The CODESYS Development System and the products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS Update area https://www.codesys.com/download/.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5.1–8.1
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (52)
Products and version ranges known to be affected.
- CODESYS Control RTE (SL)all versionsfixedcodesys_psirtDEcpe:2.3:a:codesys:codesys_control_rte_sl:3.5.22.40:*:*:*:*:*:*:*
- CODESYS Control RTE (SL)≤ vers:generic/>=3.0.0.0|<3.5.22.40codesys_psirtDEcpe:2.3:a:codesys:codesys_control_rte_sl:*:*:*:*:*:*:*:*
- CODESYS Control RTE (for Beckhoff CX) SLall versionsfixedcodesys_psirtDEcpe:2.3:a:codesys:codesys_control_rte_for_beckhoff_cx_sl:3.5.22.40:*:*:*:*:*:*:*
- CODESYS Control RTE (for Beckhoff CX) SL≤ vers:generic/>=3.0.0.0|<3.5.22.40codesys_psirtDEcpe:2.3:a:codesys:codesys_control_rte_for_beckhoff_cx_sl:*:*:*:*:*:*:*:*
advisories (2)
Vendor and ecosystem advisories describing this.
- Advisory2026-12_VDE-2026-097CODESYS Control Runtime - Improper Synchronization in Monitoring2026-09-30csaf · codesys_psirtDE
The monitoring functionality of affected CODESYS Control runtime systems processes read and write requests to PLC application data sent by the CODESYS Development System and other clients such as HMIs. Due to improper synchronization in the CmpMonitor2 component when processing concurrent requests from multiple clients, incorrect data may be read or written, potentially resulting in unexpected behavior of the affected product. PLCs based on the CODESYS Runtime Toolkit or CODESYS Safety SIL2 are affected if they allow simultaneous access by two or more clients via the CODESYS protocol. In CODESYS Development System 3, simultaneous access to the included Simulation Runtime can only occur when access by an external client, such as an HMI, has been explicitly enabled through dedicated configuration. The default configuration of CODESYS Development System 3 is not affected. The vulnerability can be exploited by an authenticated remote attacker with monitoring access by issuing concurrent requests to an affected product.
- WID-SEC-W-2026-3710CODESYS Control Runtime und Gateway Client: Mehrere SchwachstellenDeutsch2026-10-01csaf · cert_bundDE
Ein Angreifer kann mehrere Schwachstellen in CODESYS Control Runtime und Gateway Client ausnutzen, um Daten zu manipulieren und einen Denial-of-Service-Zustand herbeizuführen.
sources
Which sources assert this record, and when.
references (1) nvd
External citations — patches, advisories, analysis.
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan