CVE-2026-54429

highpriority · track · 0EPSS 0.003 · 18 %ileDEEUNLRUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.27% (18th) EPSS
CVSS 7.4 · high
Is it mine?
169 products
Check your exposure
Who says so?
7 sources
cnnvd · enisa_euvd · fstec_bdu · cert_bund

EPSS · scored 2026-10-27

A vulnerability has been identified in SIMATIC S7-PLCSIM Advanced (All versions). Affected devices do not properly handle high-volume multicast network traffic, which can exhaust available memory resources in the affected application. This could allow an unauthenticated attacker on the local network segment to cause a denial-of-service condition of the affected application. The affected application becomes inaccessible and requires a manual restart; no project data is lost. Successful exploitation requires a specific project configuration to be already active on the targeted instance.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationSIMATIC S7-PLCSIM Advancedsiemens_psirt

    Disable the S7-PLCSIM Virtual Switch binding on the network adapter used by the affected instance. This prevents the adapter from entering an external communication mode and removes the attack vector entirely. (see SIMATIC S7-PLCSIM Advanced Function Manual V8.0, 11/2025 Section 5.3 and Section 6.1.2.3; and SIMATIC S7-PLCSIM Advanced Function Manual API V8.0, 11/2025 Section 7.2)

  • MitigationSIMATIC S7-PLCSIM Advancedcisa_csaf_ot

    Disable the S7-PLCSIM Virtual Switch binding on the network adapter used by the affected instance. This prevents the adapter from entering an external communication mode and removes the attack vector entirely. (see SIMATIC S7-PLCSIM Advanced Function Manual V8.0, 11/2025 Section 5.3 and Section 6.1.2.3; and SIMATIC S7-PLCSIM Advanced Function Manual API V8.0, 11/2025 Section 7.2)

  • No fix availableSIMATIC S7-PLCSIM Advancedsiemens_psirt

    Currently no fix is available

  • No fix availableSIMATIC S7-PLCSIM Advancedcisa_csaf_ot

    Currently no fix is available

02

cvss

Technical severity, 0–10. One row per scoring source.

7.4
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · low–high · 2.3–7.4

v3.17.4highCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Hsecondary · NCSC-NL NL
v3.17.4highAV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.4highCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Hsecondary · productcert@siemens.com DEexploitability 2.8 · impact 4
v3.17.4highCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Hsecondary · Siemens ProductCERT DE
v3.17.4highCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:Hsecondary · CISA US
v4.06mediumCVSS:4.0/AV:A/AC:L/AT:P/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:Lsecondary · ENISA EU
v4.06mediumCVSS:4.0/AV:A/AC:L/AT:P/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.02.3lowCVSS:4.0/AV:A/AC:L/AT:P/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:L/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Trackcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (169)

Products and version ranges known to be affected.

06

advisories (4)

Vendor and ecosystem advisories describing this.

  • NCSC-2026-0229Kwetsbaarheden verholpen in Siemens productenNL2026-07-14csaf · ncsc_nlNL

    Siemens heeft kwetsbaarheden verholpen in diverse producten als CADRA, IAM, Mendix, OpCenter, RUGGEDCOM, SIDIS en SIMATIC.

  • SSA-828211SSA-828211: Denial of Service Vulnerability in SIMATIC S7-PLCSIM Advanced2026-07-14csaf · siemens_psirtDE

    SIMATIC S7-PLCSIM Advanced contains a vulnerability that could allow an attacker to cause a denial of service condition. Siemens is preparing fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.

  • WID-SEC-W-2026-2307Siemens SIMATIC S7: Schwachstelle ermöglicht Denial of ServiceDeutsch2026-07-13csaf · cert_bundDE

    Ein Angreifer aus einem angrenzenden Netzwerk kann eine Schwachstelle in Siemens SIMATIC S7 ausnutzen, um einen Denial of Service Angriff durchzuführen.

  • ICSA-26-209-03Siemens SIMATIC S7-PLCSIM Advanced2026-07-14icsa · cisa_csaf_otUS

    SIMATIC S7-PLCSIM Advanced contains a vulnerability that could allow an attacker to cause a denial of service condition. Siemens is preparing fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.

07

also known as (5)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (3)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan