CVE-2026-10714

highpriority · track · 0EPSS 0.001 · 4 %ileDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.15% (4th) EPSS
CVSS 7.8 · high
Is it mine?
8 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cert_bund

EPSS · scored 2026-10-27

A security issue exists within FactoryTalk® Services Platform (FTSP), allowing an attacker to bypass JWT signature validation during Okta Web Authentication. The vulnerability stems from the application not verifying that the JWT algorithm is configured for RSA, enabling an attacker to set the algorithm to "none" and craft forged tokens. This could allow an authenticated low-privilege user to impersonate any authorized user on the FTSP server, resulting in unauthorized access to system configuration and the ability to grant permissions to other systems protected by FTSP.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationFactoryTalk Directory (FTSP)cisa_csaf_ot

    Users using FactoryTalk Services Platform v6.60 should apply either the individual patch (RAID 1158263) or the February 2026 Patch Roll-up, or later update.

02

cvss

Technical severity, 0–10. One row per scoring source.

8.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5.8–8.8

v3.17.8highCVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:Hsecondary · CISA US
v3.17.8highAV:L/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v4.08.8highCVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:Hsecondary · ENISA EU
v4.08.8highCVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · PSIRT@rockwellautomation.com
v4.05.8mediumCVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (8)

Products and version ranges known to be affected.

06

advisories (2)

Vendor and ecosystem advisories describing this.

  • WID-SEC-W-2026-2335Rockwell Automation FactoryTalk Services Platform und DataMosaix Private Cloud: Mehrere SchwachstellenDeutsch2026-07-14csaf · cert_bundDE

    Ein Angreifer kann mehrere Schwachstellen in Rockwell Automation FactoryTalk Produkten ausnutzen, um seine Privilegien zu erhöhen oder Cross-Site-Scripting-Angriffe durchzuführen.

  • ICSA-26-202-07Rockwell Automation FactoryTalk Services Platform2026-07-21icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability could allow an attacker to impersonate an authorized user on the FTSP server, resulting in unauthorized access to system configurations.

07

also known as (4)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (3)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan