CVE-2025-30002

highpriority · track · 0EPSS 0.009 · 59 %ileDEEUNLRUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.88% (59th) EPSS
CVSS 8.8 · high
Is it mine?
12 products
Check your exposure
Who says so?
7 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UpdateConnectionVariables' method. This could allow an authenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on. (ZDI-CAN-25909)

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

02

cvss

Technical severity, 0–10. One row per scoring source.

8.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.3–8.8

v3.18.8highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · NCSC-NL NL
v3.18.8highAV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.18.8highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · productcert@siemens.com DEexploitability 2.8 · impact 5.9
v3.18.8highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · Siemens ProductCERT DE
v3.18.8highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.06.3mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (12)

Products and version ranges known to be affected.

06

advisories (3)

Vendor and ecosystem advisories describing this.

  • NCSC-2025-0135Kwetsbaarheden verholpen in Siemens TeleControl ServerNL2025-04-17csaf · ncsc_nlNL

    Siemens heeft kwetsbaarheden verholpen in TeleControl Server Basic.

  • SSA-443402SSA-443402: Multiple SQL Injection Vulnerabilities in TeleControl Server Basic before V3.1.2.22025-04-16csaf · siemens_psirtDE

    TeleControl Server Basic before V3.1.2.2 contains multiple SQL Injection vulnerabilities that could allow an attacker to read and write to the application's DB, cause denial of service and execute code in an OS shell with limited "NT AUTHORITY\NetworkService" permissions. Siemens has conducted a root-cause analysis for potential SQL injection vulnerabilities and has identified the locations in the code base where the underlying legacy design pattern has been used in. TeleControl Server Basic V3.1.2.2 has fixed all occurrences in the affected product. Siemens has released a new version for TeleControl Server Basic and recommends to update to the latest version.

  • ICSA-25-112-01Siemens TeleControl Server Basic SQL2025-04-16icsa · cisa_csaf_otUS

    TeleControl Server Basic before V3.1.2.2 contains multiple SQL Injection vulnerabilities that could allow an attacker to read and write to the application's DB, cause denial of service and execute code in an OS shell with limited "NT AUTHORITY\NetworkService" permissions. Siemens has conducted a root-cause analysis for potential SQL injection vulnerabilities and has identified the locations in the code base where the underlying legacy design pattern has been used in. TeleControl Server Basic V3.1.2.2 has fixed all occurrences in the affected product. Siemens has released a new version for TeleControl Server Basic and recommends to update to the latest version.