CVE-2025-2813
highpriority · track · 0EPSS 0.007 · 51 %ileDEEUEPSS · scored 2026-10-27
An unauthenticated remote attacker can cause a Denial of Service by sending a large number of requests to the http service on port 80.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- Fixedphoenix_contact_psirt
Affected bus couplers are designed and developed for the use in closed industrial networks. Phoenix Contact therefore strongly recommends using the devices exclusively in closed networks and protected by a suitable firewall. To further improve security, fixed firmware versions are available for the items listed in the "Fixed" section. A fix for products marked as "discontinued" is not planned. All other listed products will receive a bugfix at the next revision.
- MitigationBosch Rexroth AG R-IL ETH BK DI8 DO4 2TX-PAC (R911171726)bosch_psirt
If possible, protect your network by blocking access to port 80 on the affected devices.
- MitigationBosch Rexroth AG S20-EIP-BK (R911173904)bosch_psirt
If possible, protect your network by blocking access to port 80 on the affected devices.
- MitigationBosch Rexroth AG S20-ETH-BK (R911173905)bosch_psirt
If possible, protect your network by blocking access to port 80 on the affected devices.
- MitigationBosch Rexroth AG S20-PN-BK+ (R911173359)bosch_psirt
If possible, protect your network by blocking access to port 80 on the affected devices.
- Mitigationphoenix_contact_psirt
This product was designed for use in closed industrial networks. Phoenix Contact strongly recommends operating network-capable devices in closed networks or protected with a suitable firewall. For detailed information on our recommendations for measures to protect network-capable devices, please refer to our [application note](https://dam-mdc.phoenixcontact.com/asset/156443151564/0a870ae433c19148b80bd760f3a1c1f2/107913_en_03.pdf). If the use of scanners is mandatory for network security in closed production networks, it is recommended to exclude or disable denial of service tests that target port 80. Most network scanners offer options to individually disable certain tests or to apply exclusions by clustering device types and test categorization functions.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (36)
Products and version ranges known to be affected.
advisories (2)
Vendor and ecosystem advisories describing this.
- BOSCH-SA-757244BOSCH-SA-7572442025-08-14csaf · bosch_psirtDE
Several fieldbus couplers sold by Bosch Rexroth contain technology from Phoenix Contact. The manufacturer published a security bulletin about a weakness in the web-based administration interface. A successful attack leads to an overload of the device and the hardware watchdog is triggered. Process data behaves according to the configured substitute value behavior. The bus coupler requires a manual restart (resetting the power supply, pressing the reset button or executing the SNMP reset command) to reestablish communication within the Industrial Ethernet (e.g. PROFINET IO, Modbus/TCP, EtherNet/IP).
- VDE-2025-029Phoenix Contact: Security Advisory for AXL F BK and IL BK bus couplers2025-05-13csaf · phoenix_contact_psirtDE
A denial of service (DoS) attack targeting port 80 (http service) can overload the device (CWE-770). This behaviour has been observed when running network security scanners.