CVE-2025-24481

highpriority · track · 0EPSS 0.002 · 6 %ileDEEUNLUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.16% (6th) EPSS
CVSS 7.3 · high
Is it mine?
9 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · cert_bund · cisa_csaf_ot

EPSS · scored 2026-10-27

An Incorrect Permission Assignment Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect permissions being assigned to the remote debugger port and can allow for unauthenticated access to the system configuration.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationFactoryTalk View Site Editioncisa_csaf_ot

    Check the environment variables (PATH), and make sure FactoryTalk® View SE installation path (C:\Program Files (x86)\Common Files\Rockwell) is before all others

02

cvss

Technical severity, 0–10. One row per scoring source.

7.3
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.8–7.3

v3.17.3highCVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:Hsecondary · CISA US
v4.07highCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.07highCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · PSIRT@rockwellautomation.com
v4.04.8mediumCVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (9)

Products and version ranges known to be affected.

05

advisories (3)

Vendor and ecosystem advisories describing this.

  • NCSC-2025-0036Kwetsbaarheden verholpen in Rockwell Automation FactoryTalkNL2025-01-29csaf · ncsc_nlNL

    Rockwell Automation heeft kwetsbaarheden verholpen in FactoryTalk View Site.

  • WID-SEC-W-2025-0205Rockwell Automation FactoryTalk (View SE): Mehrere SchwachstellenDeutsch2025-01-28csaf · cert_bundDE

    Ein lokaler Angreifer kann mehrere Schwachstellen in Rockwell Automation FactoryTalk ausnutzen, um seine Privilegien zu erhöhen oder Sicherheitsmaßnahmen zu umgehen.

  • ICSA-25-028-04Rockwell Automation FactoryTalk View Site Edition2025-01-28icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities could allow an attacker to gain unauthenticated access to system configuration files and execute DLLs with elevated privileges.