CVE-2025-11482

highpriority · track · 0EPSS 0.003 · 25 %ileCHEUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.32% (25th) EPSS
CVSS 7.5 · high
Is it mine?
7 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · abb_psirt · cisa_csaf_ot

EPSS · scored 2026-10-26

An Allocation of Resources Without Limits or Throttling vulnerability in the OPC-UA Server used in PPT30 Operating System versions before 1.8.0 may be used by an unauthenticated network-based attacker to permanently prevent legitimate users from interacting with the service.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedPPT30 Operating Systemabb_psirt

    The problem is corrected in the following product versions: PPT30 Operating System 1.8.0 The OPC-UA server is not activated by default. B&R recommends that customers with the OPC-UA Server enabled to install the update at their earliest opportunity. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.

  • FixedPPT30 Operating Systemcisa_csaf_ot

    The problem is corrected in the following product versions: PPT30 Operating System 1.8.0. The OPC-UA server is not activated by default. B&R recommends that customers with the OPC-UA Server enabled to install the update at their earliest opportunity. The process to install updates is described in the user manual. The step to identify the installed product version is described in the user manual.

  • MitigationPPT30 Operating Systemabb_psirt

    The optional OPC-UA server is not activated by default. The OPC-UA server shall only be activated, if required. PPT30 products are intended to operate at Levels 1 and 2 of the ABB ICS Cyber Security Reference Architecture. To restrict access to the OPC-UA server exclusively to trusted IP addresses, configure the South Firewall and/or the Control Network Firewall accordingly, and properly segment the network where the PPT30 operates. Additionally, ensure that the physical network interfaces assigned to the same logical network as the PPT30 are accessible only to authorized personnel. Refer to section “General security recommendations” for further advise on how to keep your system secure.

  • MitigationPPT30 Operating Systemcisa_csaf_ot

    The optional OPC-UA server is not activated by default. The OPC-UA server shall only be activated, if required. PPT30 products are intended to operate at Levels 1 and 2 of the ABB ICS Cyber Security Reference Architecture. To restrict access to the OPC-UA server exclusively to trusted IP addresses, configure the South Firewall and/or the Control Network Firewall accordingly, and properly segment the network where the PPT30 operates. Additionally, ensure that the physical network interfaces assigned to the same logical network as the PPT30 are accessible only to authorized personnel. Refer to section “General security recommendations” for further advise on how to keep your system secure.

02

cvss

Technical severity, 0–10. One row per scoring source.

8.7
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.6–8.7

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:U/RL:O/RC:Csecondary · CISA US
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · cybersecurity@ch.abb.comexploitability 3.9 · impact 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:U/RL:O/RC:Csecondary · ABB PSIRT
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.7highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@ch.abb.com
v4.06.6mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (7)

Products and version ranges known to be affected.

06

advisories (2)

Vendor and ecosystem advisories describing this.

  • SA25P006PPT30 OPC-UA Server has issues handling concurrent connections2026-05-26csaf · abb_psirtCH

    B&R is aware of a vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploits this vulnerability could make the OPC-UA server of the product inaccessible.

  • ICSA-26-155-03B&R PPT30 Operating System2026-05-26icsa · cisa_csaf_otUS

    B&R is aware of a vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploits this vulnerability could make the OPC-UA server of the product inaccessible.

07

also known as (3)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (4)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan