CVE-2024-8531

highpriority · track · 0EPSS 0.005 · 40 %ileEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.46% (40th) EPSS
CVSS 7.2 · high
Is it mine?
6 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

CWE-347: Improper Verification of Cryptographic Signature vulnerability exists that could compromise the Data Center Expert software when an upgrade bundle is manipulated to include arbitrary bash scripts that are executed as root.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedData Center Expertcisa_csaf_ot

    Version 8.2 of EcoStruxure™ IT Data Center Expert includes fixes for these vulnerabilities and is available upon request from Schneider Electric’s Customer Care Center.

  • MitigationData Center Expertcisa_csaf_ot

    Ensure that the principals of least privilege are being followed so that only those with need have account access and that the level of their respective account authorization aligns with their role, including Privileged Accounts as described in the Data Center Expert Security Handbook. • Verify SHA1 checksums of upgrade bundles prior to executing upgrades as described in the Upgrades section of the Data Center Expert Security Handbook.. • Delete any existing “logcapture” archives present on the system and do not create any new “logcapture” archives. Existing archives can be deleted from the https://server_ip/capturelogs web page after authenticating.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.2
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.6–7.2

v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.17.2highAV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · ENISA EU
v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · cybersecurity@se.comexploitability 1.2 · impact 5.9
v3.16.6mediumCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (6)

Products and version ranges known to be affected.

06

advisories (2)

Vendor and ecosystem advisories describing this.

  • ICSA-24-289-02Schneider Electric Data Center Expert2024-10-08icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its Data Center Expert product. The Data Center Expert product is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment. Failure to apply the fix provided below may risk information disclosure, which could result in access to private data.

  • ICSA-25-016-08Schneider Electric Data Center Expert2024-10-08icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its Data Center Expert product. The Data Center Expert product is a scalable monitoring software that collects, organizes, and distributes critical device information providing a comprehensive view of equipment. Failure to apply the fix provided below may risk information disclosure, which could result in access to private data.

07

also known as (6)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (4)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.