CVE-2024-8175

highpriority · track · 0EPSS 0.006 · 49 %ileCHDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.62% (49th) EPSS
CVSS 7.5 · high
Is it mine?
90 products
Check your exposure
Who says so?
9 sources
cnnvd · enisa_euvd · fstec_bdu · abb_psirt

EPSS · scored 2026-10-22

An unauthenticated remote attacker can causes the CODESYS web server to access invalid memory which results in a DoS.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedAC500 V3abb_psirt

    The problem is corrected in AC500 V3 firmware version 3.8.0. ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0.

  • Fixedcodesys_psirt

    Update the following products to version 3.5.20.30. * CODESYS Control RTE (SL) * CODESYS Control RTE (for Beckhoff CX) SL * CODESYS Control Win (SL) * CODESYS HMI (SL) * CODESYS Runtime Toolkit * CODESYS Embedded Target Visu Toolkit * CODESYS Remote Target Visu Toolkit The products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS download area.

  • FixedControl for IOT2000 SLcodesys_psirt

    Update the following product to version 4.15.0.0 (Version 4.14.0.0 has not been released). * CODESYS Control for IOT2000 SL The products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS download area.

  • FixedFirmware <=01.03.03 (FW3) installed on Basic Controller 0750-8001wago_psirt

    Update to Firmware version 01.04.07 (FW4).

  • FixedFirmware <=01.03.03 (FW3) installed on Basic Controller 0751-8000wago_psirt

    Update to Firmware version 01.04.07 (FW4).

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · info@cert.vde.comexploitability 3.9 · impact 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · WAGO PSIRT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Festo PSIRT DE
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ABB PSIRT
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CODESYS PSIRT
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (90)

Products and version ranges known to be affected.

06

advisories (6)

Vendor and ecosystem advisories describing this.

  • 3ADR011377AC500 V3 Multiple vulnerabilities2025-01-07csaf · abb_psirtCH

    An update is available that resolves a publicly reported vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploited these vulnerabilities could call shell functions (CVE-2023-6357), crash the PLC (CVE-2024-5000), crash the web server of the PLC (CVE-2024-8175), grant read access to files (CVE-2024-12429) or enable command execution (CVE-2024-12430). The vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430 require successful authentication.

  • Advisory2024-05_VDE-2024-057CODESYS: CODESYS web server vulnerable to DoS2024-09-25csaf · codesys_psirtDE

    The CODESYS web server component of the CODESYS Control runtime system is used by the CODESYS WebVisu to display visualization screens in a web browser. Receiving a specifically crafted TLS packet on an HTTPS connection causes the CODESYS web server to crash because the return value of an underlying function is not checked correctly for such unusual conditions.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2024-072WAGO: Vulnerabilities in CODESYS Control2024-12-03csaf · wago_psirtDE

    The following firmware versions installed on several devices are vulnerable due to a vulnerability in the CODESYS Control V3 web server.

  • WID-SEC-W-2024-2208CODESYS: Schwachstelle ermöglicht Denial of ServiceDeutsch2024-09-23csaf · cert_bundDE

    Ein entfernter, anonymer Angreifer kann eine Schwachstelle in CODESYS ausnutzen, um einen Denial of Service Angriff durchzuführen.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

07

also known as (4)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (8)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan