A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V05.30). The affected devices contain a secure element which is connected via an unencrypted SPI bus. This could allow an attacker with physical access to the SPI bus to observe the password used for the secure element authentication, and then use the secure element as an oracle to decrypt all encrypted update files.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedCPCI85 Central Processing/Communicationsiemens_psirt
Update to V05.30 or later version
- FixedCPCI85 Central Processing/Communicationcisa_csaf_ot
Update to V05.30 or later version
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · low–medium · 1.7–5.1
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (7)
Products and version ranges known to be affected.
- cpci85_central_processing_communicationall versionsncsc_nlNLcpe:2.3:a:siemens:cpci85_central_processing_communication:*:*:*:*:*:*:*:*
advisories (4)
Vendor and ecosystem advisories describing this.
- NCSC-2024-0473Kwetsbaarheden verholpen in Siemens productenNL2024-12-10csaf · ncsc_nlNL
Siemens heeft kwetsbaarheden verholpen in diverse producten als COMOS, RUGGEDCOM, SENTRON, SICAM, SIMATIC en TeamCenter.
- SSA-128393SSA-128393: Firmware Decryption Vulnerability in SICAM A8000 CP-8031 and CP-80502024-12-10csaf · siemens_psirtDE
The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware. Siemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions. Both the firmware and the hardware update are required to fix the vulnerability. For details see the section "Additional Information".
- WID-SEC-W-2024-3655Siemens SICAM: Schwachstelle ermöglicht Offenlegung von InformationenDeutsch2024-12-10csaf · cert_bundDE
Ein Angreifer mit physischem Zugriff kann eine Schwachstelle in Siemens SICAM ausnutzen, um Informationen offenzulegen.
- ICSA-24-347-01Siemens CPCI85 Central Processing/Communication 2024-12-10icsa · cisa_csaf_otUS
The SICAM A8000 CP-8031 and CP-8050 devices are affected by a vulnerability that could allow an attacker with physical access to the device to decrypt the firmware. Siemens has released new firmware and hardware versions for the affected products and recommends to update to the latest versions. Both the firmware and the hardware update are required to fix the vulnerability. For details see the section "Additional Information".
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (4)
External citations — patches, advisories, analysis.
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan