CVE-2024-5000
highpriority · track · 0EPSS 0.006 · 46 %ileCHDEEUUSEPSS · scored 2026-10-22
An unauthenticated remote attacker can use a malicious OPC UA client to send a crafted request to affected CODESYS products which can cause a DoS due to incorrect calculation of buffer size.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedAC500 V3abb_psirt
The problem is corrected in AC500 V3 firmware version 3.8.0. ABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0.
- Fixedcodesys_psirt
Update the following products to version 3.5.20.10: • CODESYS Control RTE (SL) • CODESYS Control RTE (for Beckhoff CX) SL • CODESYS Control Win (SL) • CODESYS Runtime Toolkit • CODESYS HMI (SL) Update the following products to version 4.12.0.0: • CODESYS Control for BeagleBone SL • CODESYS Control for emPC-A/iMX6 SL • CODESYS Control for IOT2000 SL • CODESYS Control for Linux ARM SL • CODESYS Control for Linux SL • CODESYS Control for PFC100 SL • CODESYS Control for PFC200 SL • CODESYS Control for PLCnext SL • CODESYS Control for Raspberry Pi SL • CODESYS Control for WAGO Touch Panels 600 SL The products available as CODESYS add-ons can be downloaded and installed directly with the CODESYS Installer or be downloaded from the CODESYS Store. Alternatively, as well as for all other products, you will find further information on obtaining the software update in the CODESYS download area.
- FixedFirmware <01.04.07(FW4 Basic Controller) installed on Basic Controller 100 0750-800xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <03.10.11(FW22Patch2) installed on PFC100 G1 0750-810x/xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <03.10.11(FW22Patch2) installed on PFC200 G1 750-820x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on CC100 0751-9x01wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on Edge Controller 0752-8303/8000-0002wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on PFC100 G2 0750-811x-xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on PFC200 G2 750-821x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-420x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-430x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-520x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-530x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-620x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.05.10(FW27) installed on TP600 0762-630x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on Edge Controller 0752-8303/8000-0002wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on PFC100 G2 0750-811x-xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on PFC200 G2 750-821x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-420x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-430x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-520x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-530x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-620x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.01(70) installed on TP600 0762-630x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- FixedFirmware <04.06.03(70) installed on CC100 0751-9x01wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt
Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.
- MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt
Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.
- Mitigationcodesys_psirt
Starting from version 3.5.15.0 of the affected products, the incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 or less. This can be achieved by adding the following setting in the CODESYS runtime configuration file (e.g. CODESYSControl.cfg): [CmpOPCUAStack] Stack.MaxArrayLenth=10129639
- MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot
Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.
- MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot
Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.
- WorkaroundFirmware <01.04.07(FW4 Basic Controller) installed on Basic Controller 100 0750-800xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <03.10.11(FW22Patch2) installed on PFC100 G1 0750-810x/xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <03.10.11(FW22Patch2) installed on PFC200 G1 750-820x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on CC100 0751-9x01wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on Edge Controller 0752-8303/8000-0002wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on PFC100 G2 0750-811x-xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on PFC200 G2 750-821x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-420x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-430x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-520x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-530x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-620x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.05.10(FW27) installed on TP600 0762-630x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on Edge Controller 0752-8303/8000-0002wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on PFC100 G2 0750-811x-xxxx-xxxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on PFC200 G2 750-821x-xxx-xxxwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-420x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-430x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-520x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-530x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-620x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.01(70) installed on TP600 0762-630x/8000-000xwago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
- WorkaroundFirmware <04.06.03(70) installed on CC100 0751-9x01wago_psirt
The incorrect calculation of the buffer size can be avoided if the maximum supported array length of the OPC UA stack of the CODESYS Control runtime system is limited to a value of 10129639 (Stack.MaxArrayLenth=10129639) or less. This can be achieved by adding the following setting in the runtime configuration under the following path: /etc/codesys3.d/codesyscotrol.cfg
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–8.8
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (107)
Products and version ranges known to be affected.
- CODESYS Development System 3.5.21.20 external component of Festo Automation Suite 2.8.0.138all versionsfixedcisa_csaf_otUScpe:2.3:a:codesys:development_system:3.5.21.20*:*:*:*:*:*:*:*
- Festo Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0all versionscisa_csaf_otUScpe:2.3:a:codesys:development_system:3.0:*:*:*:*:*:*:*
- Festo Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10all versionscisa_csaf_otUScpe:2.3:a:codesys:development_system:3.5.16.10:*:*:*:*:*:*:*
advisories (6)
Vendor and ecosystem advisories describing this.
- 3ADR011377AC500 V3 Multiple vulnerabilities2025-01-07csaf · abb_psirtCH
An update is available that resolves a publicly reported vulnerability in the product versions listed as affected in the advisory. An attacker who successfully exploited these vulnerabilities could call shell functions (CVE-2023-6357), crash the PLC (CVE-2024-5000), crash the web server of the PLC (CVE-2024-8175), grant read access to files (CVE-2024-12429) or enable command execution (CVE-2024-12430). The vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430 require successful authentication.
- FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE
Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.
- VDE-2024-026CODESYS: Vulnerability can cause a DoS on CODESYS OPC UA products2024-06-04csaf · codesys_psirtDE
The CODESYS OPC UA stack of the CODESYS Control runtime system may incorrectly calculate the required buffer size for received requests/responses. This can lead to a crash of the CODESYS runtime system during the subsequent initialization of the receive buffer with zero. Update: 10.07.2024 In the Remediation section, the release date of the update has been deleted as the update is now available.
- VDE-2025-009WAGO: Vulnerabilities in CODESYS Control V3 - OPC UA Stack2025-02-04csaf · wago_psirtDE
Several WAGO Firmwares are vulnerable to an incorrect calculation of the buffer size in the CODESYS OPC UA STACK. This can lead to a crash of the runtime of the affected firmware versions installed on several devices.
- WID-SEC-W-2024-1285CODESYS: Mehrere SchwachstellenDeutsch2024-06-03csaf · cert_bundDE
Ein Angreifer kann mehrere Schwachstellen in CODESYS ausnutzen, um einen Denial-of-Service-Zustand zu erzeugen, Dateien zu manipulieren oder vertrauliche Informationen offenzulegen.
- ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS
Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (7)
External citations — patches, advisories, analysis.
- https://cert.vde.com/en/advisories/VDE-2024-026cnnvd
- https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=18355&token=e3e5a937ce72602bec39718ddc2f4ba6d983ccd1&download=cnnvd
- https://cxsecurity.com/cveshow/CVE-2024-5000/cnnvd
- https://cert.vde.com/en/advisories/VDE-2024-026enisa_euvd
- https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=18355&token=e3e5a937ce72602bec39718ddc2f4ba6d983ccd1&download=enisa_euvd
- https://cert.vde.com/en/advisories/VDE-2024-026nvd
- https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=18355&token=e3e5a937ce72602bec39718ddc2f4ba6d983ccd1&download=nvd