CVE-2024-31485

highpriority · track · 1EPSS 0.024 · 84 %ileDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.44% (84th) EPSS
CVSS 7.2 · high
Is it mine?
12 products
Check your exposure
Who says so?
6 sources
cnnvd · enisa_euvd · fstec_bdu · cert_bund

EPSS · scored 2026-10-27

A vulnerability has been identified in CPCI85 Central Processing/Communication (All versions < V5.30), SICORE Base system (All versions < V1.3.0). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedCPCI85 Central Processing/Communicationsiemens_psirt

    Update to V5.30 or later version The firmware CPCI85 V5.30 is present within "CP-8031/CP-8050 Package" V5.30

  • FixedSICORE Base systemsiemens_psirt

    Update to V1.3.0 or later version The firmware SICORE V1.3.0 is present within "SICAM 8 Software Solution Package" V5.30

  • FixedCPCI85 Central Processing/Communicationcisa_csaf_ot

    Update to V5.30 or later version The firmware CPCI85 V5.30 is present within "CP-8031/CP-8050 Package" V5.30

  • FixedSICORE Base systemcisa_csaf_ot

    Update to V1.3.0 or later version The firmware SICORE V1.3.0 is present within "SICAM 8 Software Solution Package" V5.30

02

cvss

Technical severity, 0–10. One row per scoring source.

8.6
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.1–8.6

v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · productcert@siemens.com DEexploitability 1.2 · impact 5.9
v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · Siemens ProductCERT DE
v3.17.2highAV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.17.2highCVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v4.08.6highCVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · productcert@siemens.com DE
v4.08.6highCVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.06.1mediumCVSS:4.0/AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: poc · Automatable: no · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (12)

Products and version ranges known to be affected.

06

advisories (3)

Vendor and ecosystem advisories describing this.

  • SSA-871704SSA-871704: Multiple Vulnerabilities in SICAM Products2024-05-14csaf · siemens_psirtDE

    Multiple SICAM products are affected by vulnerabilities that could lead to privilege escalation, remote code execution or information loss namely: - SICAM A8000 device firmwares - CPC80 for CP-8000/CP-8021/CP-8022 - CPCI85 and OPUPI0 for CP-8031/CP-8050 - SICAM EGS firmware - CPCI85 and OPUPI0 - SICAM 8 Software Solution - SICORE Siemens has released new versions for the affected firmwares and recommends to update to the latest versions.

  • WID-SEC-W-2024-1111Siemens SICAM: Mehrere SchwachstellenDeutsch2024-05-13csaf · cert_bundDE

    Ein entfernter, anonymer oder authentisierter Angreifer kann mehrere Schwachstellen in Siemens SICAM ausnutzen, um beliebigen Programmcode auszuführen und um um vertrauliche Informationen offenzulegen.

  • ICSA-24-137-02Siemens SICAM Products2024-05-14icsa · cisa_csaf_otUS

    Multiple SICAM products are affected by vulnerabilities that could lead to privilege escalation, remote code execution or information loss namely: - SICAM A8000 device firmwares - CPC80 for CP-8000/CP-8021/CP-8022 - CPCI85 and OPUPI0 for CP-8031/CP-8050 - SICAM EGS firmware - CPCI85 and OPUPI0 - SICAM 8 Software Solution - SICORE Siemens has released new versions for the affected firmwares and recommends to update to the latest versions.

07

also known as (5)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (7)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan