EPSS · scored 2026-10-27

A vulnerability has been identified in SENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75) (All versions). Affected devices expose an unused, unstable http service at port 80/tcp on the Modbus-TCP Ethernet. This could allow an attacker on the same Modbus network to create a denial of service condition that forces the device to reboot.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationSENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75)siemens_psirt

    Restrict access to the Modbus-TCP network by blocking incoming connections to port 80/tcp, e.g. in a firewall

  • MitigationSENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75)cisa_csaf_ot

    Restrict access to the Modbus-TCP network by blocking incoming connections to port 80/tcp, e.g. in a firewall

  • No fix availableSENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75)siemens_psirt

    Currently no fix is available

  • No fix availableSENTRON 3KC ATC6 Expansion Module Ethernet (3KC9000-8TL75)cisa_csaf_ot

    Currently no fix is available

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · productcert@siemens.com DEexploitability 3.9 · impact 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Siemens ProductCERT DE
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (6)

Products and version ranges known to be affected.

06

advisories (2)

Vendor and ecosystem advisories describing this.

  • SSA-918992SSA-918992: Unused HTTP Service on SENTRON 3KC ATC6 Ethernet Module2024-03-12csaf · siemens_psirtDE

    SENTRON 3KC ATC6 Expansion Module Ethernet exposes an unused, unstable http service at port 80/tcp on the Modbus-TCP Ethernet, which could allow an attacker on the same Modbus network to create a denial of service condition that forces the device to reboot. Siemens is preparing fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.

  • ICSA-24-074-06Siemens SENTRON2024-03-12icsa · cisa_csaf_otUS

    SENTRON 3KC ATC6 Expansion Module Ethernet exposes an unused, unstable http service at port 80/tcp on the Modbus-TCP Ethernet, which could allow an attacker on the same Modbus network to create a denial of service condition that forces the device to reboot. Siemens is preparing fix versions and recommends specific countermeasures for products where fixes are not, or not yet available.