CVE-2024-11737

criticalpriority · track · 0EPSS 0.006 · 50 %ileEUNLRUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.64% (50th) EPSS
CVSS 9.8 · critical
Is it mine?
24 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-23

CWE-20: Improper Input Validation vulnerability exists that could lead to a denial of service and a loss of confidentiality, integrity of the controller when an unauthenticated crafted Modbus packet is sent to the device.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedModicon Controllers LMC058cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • FixedModicon Controllers M241cisa_csaf_ot

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • FixedModicon Controllers M251cisa_csaf_ot

    Modicon M241/M251 Firmware version 5.2.11.29 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application that is part of EcoStruxure Machine Expert: https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ By using Controller Assistant update Modicon Controller M241/M251 to the latest Firmware and perform reboot.

    https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/
  • FixedModicon Controllers M258cisa_csaf_ot

    Modicon M258/LMC058 Firmware version 5.0.4.19 includes a fix for this vulnerability and can be downloaded here: https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware By using Controller Assistant from EcoStruxureTM Machine Expert update Modicon Controller M258/LMC058 and perform reboot.

    https://www.se.com/ww/en/product-range/2730-modicon-m258-compact-plc-for-machine-automation/#software-and-firmware
  • MitigationModicon Controllers LMC058cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M241cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M251cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
  • MitigationModicon Controllers M258cisa_csaf_ot

    If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of ex * Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. * Filter ports and IP through the embedded firewall. * Set up network segmentation and implement a firewall to block all unauthorized access to port 502/TCP. * Disable all unused protocols (default configuration). * For more details refer to “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment User Guide”: https://www.se.com/ww/en/download/document/EIO0000004242/

    https://www.se.com/ww/en/download/document/EIO0000004242/
02

cvss

Technical severity, 0–10. One row per scoring source.

9.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · high–critical · 8.1–9.8

v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · cybersecurity@se.comexploitability 3.9 · impact 5.9
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · NCSC-NL NL
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · cybersecurity@se.com
v4.09.3criticalCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:Nsecondary · ENISA EU
v4.08.1highCVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:U/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:Xsecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (24)

Products and version ranges known to be affected.

showing 20 of 24
06

advisories (2)

Vendor and ecosystem advisories describing this.

  • NCSC-2024-0489Kwetsbaarheid verholpen in Schneider Electric ModiconNL2024-12-13csaf · ncsc_nlNL

    Schneider Electric heeft een kwetsbaarheid verholpen in apparaten die het Modbus-protocol gebruiken.

  • ICSA-24-352-04Schneider Electric Modicon2024-12-10icsa · cisa_csaf_otUS

    Schneider Electric is aware of a vulnerability in its Modicon M241 / M251 / M258 https://www.se.com/ww/en/product-category/3900-plc-pac-and-dedicated-controllers/ and Modicon LMC058 https://www.se.com/ww/en/product-range/7744-modicon-lmc058/ products. The Modicon M241/M251/M258/LMC058 products are Programmable Logic Controllers for performance-demanding applications. Failure to apply the Fix provided below may risk a denial of service and partial loss of Integrity of the controller, which could result in disruption operations. October 2025 Update: A remediation is now available for Modicon M258 / LMC058

07

also known as (4)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (3)

External citations — patches, advisories, analysis.

scry