CVE-2023-36380

highpriority · track · 31OT risk · elevatedEPSS 0.004 · 35 %ileDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.41% (35th) EPSS
CVSS 7.8 · high
Is it mine?
19 products
Check your exposure
Who says so?
7 sources
cnnvd · enisa_euvd · fstec_bdu · cert_bund

EPSS · scored 2026-10-26

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)). The affected devices contain a hard-coded ID in the SSH `authorized_keys` configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

02

cvss

Technical severity, 0–10. One row per scoring source.

9.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · high–critical · 7.1–9.8

v3.17.8highCVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:Hprimary · NVD / NIST USexploitability 1.8 · impact 5.9
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · ENISA EU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · productcert@siemens.com DEexploitability 3.9 · impact 5.9
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
v3.17.1highCVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (19)

Products and version ranges known to be affected.

06

advisories (3)

Vendor and ecosystem advisories describing this.

  • SSA-134651SSA-134651: Hard Coded SSH ID in CPCI85 Firmware of SICAM A8000 Devices2023-10-10csaf · siemens_psirtDE

    The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 contains a hard-coded ID in the SSH authorized_keys configuration file. An attacker with knowledge of the corresponding credential could login to the device via SSH. Only devices with activated debug support are affected. Siemens has released updates for the affected products and recommends to update to the latest versions.

  • WID-SEC-W-2023-2603Siemens SICAM: Mehrere SchwachstellenDeutsch2023-10-09csaf · cert_bundDE

    Ein entfernter, anonymer oder lokaler Angreifer kann mehrere Schwachstellen in Siemens SICAM ausnutzen, um beliebigen Code auszuführen, Sicherheitsmaßnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszulösen, seine Privilegien zu erweitern und Daten zu manipulieren.

  • ICSA-23-285-09Siemens CPCI85 Firmware of SICAM A8000 Devices2023-10-10icsa · cisa_csaf_otUS

    The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 contains a hard-coded ID in the SSH authorized_keys configuration file. An attacker with knowledge of the corresponding credential could login to the device via SSH. Only devices with activated debug support are affected. Siemens has released updates for the affected products and recommends to update to the latest versions.

07

also known as (5)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (5)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.