CVE-2023-28489

criticalpriority · track · 40EPSS 0.028 · 87 %ileDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
2.84% (87th) EPSS
CVSS 9.8 · critical
Is it mine?
12 products
Check your exposure
Who says so?
7 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-26

A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default. The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

02

cvss

Technical severity, 0–10. One row per scoring source.

9.8
010

base score 0–10 · higher = more severe · hover a vector to decode

v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 5.9
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · CISA US
v3.19.8criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · FSTEC (BDU) RU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · ENISA EU
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · productcert@siemens.com DEexploitability 3.9 · impact 5.9
v3.19.8criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:Csecondary · Siemens ProductCERT DE
v3.19criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: totalcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (12)

Products and version ranges known to be affected.

06

advisories (3)

Vendor and ecosystem advisories describing this.

  • SSA-472454SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices2023-04-11csaf · siemens_psirtDE

    The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by unauthenticated command injection vulnerability. This could allow an attacker to perfom remote code execution. Siemens has released updates for the affected products and recommends to update to the latest versions.

  • WID-SEC-W-2023-0908Siemens SICAM A8000 Geräte: Schwachstelle ermöglicht CodeausführungDeutsch2023-04-10csaf · cert_bundDE

    Ein entfernter, anonymer Angreifer kann eine Schwachstelle in Siemens SICAM A8000 Geräten ausnutzen, um beliebigen Programmcode auszuführen.

  • ICSA-23-103-07Siemens CPCI85 Firmware of SICAM A8000 Devices2023-04-11icsa · cisa_csaf_otUS

    The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by unauthenticated command injection vulnerability. This could allow an attacker to perfom remote code execution. Siemens has released updates for the affected products and recommends to update to the latest versions.