CVE-2022-4608

highpriority · track · 30EPSS 0.007 · 53 %ileDEEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.71% (53rd) EPSS
CVSS 7.5 · high
Is it mine?
9 products
Check your exposure
Who says so?
6 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • FixedRTU500 Series CMUcisa_csaf_ot

    Hitachi Energy recommends users update to CMU Firmware versions 13.3.3 or 13.4.1.

  • MitigationRTU500 Series CMUcisa_csaf_ot

    Do not use process control systems for internet surfing, instant messaging, or receiving emails.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5

v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · cybersecurity@hitachienergy.comexploitability 3.9 · impact 3.6
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (9)

Products and version ranges known to be affected.

06

advisories (2)

Vendor and ecosystem advisories describing this.

  • WID-SEC-W-2023-2016Hitachi Energy RTU500: Mehrere SchwachstellenDeutsch2023-08-08csaf · cert_bundDE

    Ein entfernter, anonymer Angreifer kann mehrere Schwachstellen in Hitachi Energy RTU500 ausnutzen, um einen Denial of Service Angriff durchzuführen.

  • ICSA-23-220-02Hitachi Energy RTU500 series2023-08-08icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities could cause a buffer overflow and reboot of the product.