CVE-2022-29884
highpriority · track · 30EPSS 0.013 · 70 %ileDEEUUSEPSS · scored 2026-10-21
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < CPC80 V16.30), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < CPC80 V16.30), CP-8021 MASTER MODULE (All versions < CPC80 V16.30), CP-8022 MASTER MODULE WITH GPRS (All versions < CPC80 V16.30). When using the HTTPS server under specific conditions, affected devices do not properly free resources. This could allow an unauthenticated remote attacker to put the device into a denial of service condition.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
A vendor fix is available.
- FixedCP-8000 MASTER MODULE WITH I/O -25/+70°Csiemens_psirt
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8000 MASTER MODULE WITH I/O -40/+70°Csiemens_psirt
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8021 MASTER MODULEsiemens_psirt
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8022 MASTER MODULE WITH GPRSsiemens_psirt
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8000 MASTER MODULE WITH I/O -25/+70°Ccisa_csaf_ot
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8000 MASTER MODULE WITH I/O -40/+70°Ccisa_csaf_ot
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8021 MASTER MODULEcisa_csaf_ot
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - FixedCP-8022 MASTER MODULE WITH GPRScisa_csaf_ot
Update to CPC80 V16.30 or later version
https://support.industry.siemens.com/cs/ww/en/view/109811278/ - WorkaroundCP-8000 MASTER MODULE WITH I/O -25/+70°Csiemens_psirt
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8000 MASTER MODULE WITH I/O -40/+70°Csiemens_psirt
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8021 MASTER MODULEsiemens_psirt
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8022 MASTER MODULE WITH GPRSsiemens_psirt
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8000 MASTER MODULE WITH I/O -25/+70°Ccisa_csaf_ot
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8000 MASTER MODULE WITH I/O -40/+70°Ccisa_csaf_ot
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8021 MASTER MODULEcisa_csaf_ot
Limit access to port 443/tcp to trusted IP addresses
- WorkaroundCP-8022 MASTER MODULE WITH GPRScisa_csaf_ot
Limit access to port 443/tcp to trusted IP addresses
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.5
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (19)
Products and version ranges known to be affected.
- siemens sicam a8000 cp-8000 firmware< 16.30nvdUScpe:2.3:o:siemens:sicam_a8000_cp-8000_firmware:*:*:*:*:*:*:*:*
- siemens sicam a8000 cp-8021 firmware< 16.30nvdUScpe:2.3:o:siemens:sicam_a8000_cp-8021_firmware:*:*:*:*:*:*:*:*
- siemens sicam a8000 cp-8022 firmware< 16.30nvdUScpe:2.3:o:siemens:sicam_a8000_cp-8022_firmware:*:*:*:*:*:*:*:*
advisories (2)
Vendor and ecosystem advisories describing this.
- SSA-491621SSA-491621: Denial of Service Vulnerability in CPC80 Firmware of SICAM A8000 Devices2022-07-12csaf · siemens_psirtDE
A vulnerability was identified in the CPC80 firmware of SICAM A8000 devices. It could allow an unauthenticated remote attacker to cause a permanent denial of service condition. Siemens has released updates for the affected products and recommends to update to the latest versions.
- ICSA-22-195-14Siemens CPC80 Firmware of SICAM A80002022-07-12icsa · cisa_csaf_otUS
A vulnerability was identified in the CPC80 firmware of SICAM A8000 devices. It could allow an unauthenticated remote attacker to cause a permanent denial of service condition. Siemens has released updates for the affected products and recommends to update to the latest versions.
also known as (3)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (6)
External citations — patches, advisories, analysis.
- https://cert-portal.siemens.com/productcert/pdf/ssa-491621.pdfcnnvd
- https://cxsecurity.com/cveshow/CVE-2022-29884/cnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-195-14cnnvd
- https://www.cybersecurity-help.cz/vdb/SB2022071329cnnvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-491621.pdfenisa_euvd
- https://cert-portal.siemens.com/productcert/pdf/ssa-491621.pdfPatchVendor Advisorynvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.