CVE-2022-28613

highpriority · track · 30EPSS 0.010 · 62 %ileEURUUS
grimoire priorityP2 · Scheduled
Exploitable?
—
no known exploitation
Likely / severe?
0.99% (62nd) EPSS
CVSS 7.8 · high
Is it mine?
25 products
Check your exposure
Who says so?
5 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

  • MitigationRTU500 series CMU Firmwarecisa_csaf_ot

    Because the vulnerability affects only the RTU500 series with HCI Modbus TCP configured and enabled, a possible mitigation is to disable the HCI Modbus TCP function if not used. The HCI Modbus TCP is disabled by default.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.8

v2.07.8highAV:N/AC:L/Au:N/C:N/I:N/A:Cprimary · NVD / NIST USexploitability 10 · impact 6.9
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.07.5highCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · ENISA EU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · cybersecurity@hitachienergy.comexploitability 3.9 · impact 3.6
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (25)

Products and version ranges known to be affected.

05

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-22-242-04Hitachi Energy RTU500 series2022-08-30icsa · cisa_csaf_otUS

    Successful exploitation of this vulnerability could cause an internal buffer overflow, which can reboot the product.

06

also known as (5)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

09

references (8)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.