CVE-2022-28613
highpriority · track · 30EPSS 0.010 · 62 %ileEURUUSEPSS · scored 2026-10-27
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
No vendor fix yet; a mitigation is available.
- MitigationRTU500 series CMU Firmwarecisa_csaf_ot
Because the vulnerability affects only the RTU500 series with HCI Modbus TCP configured and enabled, a possible mitigation is to disable the HCI Modbus TCP function if not used. The HCI Modbus TCP is disabled by default.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 6.9–7.8
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (25)
Products and version ranges known to be affected.
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-22-242-04Hitachi Energy RTU500 series2022-08-30icsa · cisa_csaf_otUS
Successful exploitation of this vulnerability could cause an internal buffer overflow, which can reboot the product.
also known as (5)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (8)
External citations — patches, advisories, analysis.
- https://cxsecurity.com/cveshow/CVE-2022-28613/cnnvd
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launchcnnvd
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launchcnnvd
- https://us-cert.cisa.gov/ics/advisories/icsa-22-242-04cnnvd
- https://www.auscert.org.au/bulletins/ESB-2022.4286cnnvd
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launchenisa_euvd
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launchnvd
- https://search.abb.com/library/Download.aspx?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launchnvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.