CVE-2021-36764

mediumpriority · track · 30EPSS 0.010 · 62 %ileDEEURUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
0.99% (62nd) EPSS
CVSS 5 · medium
Is it mine?
34 products
Check your exposure
Who says so?
6 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-22

In CODESYS Gateway V3 before 3.5.17.10, there is a NULL Pointer Dereference. Crafted communication requests may cause a Null pointer dereference in the affected CODESYS products and may result in a denial-of-service condition.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

A vendor fix is available.

  • Fixedpilz_psirt

    PMI 6 primo, PMCprimo C: No product-specific countermeasures available, please follow the general countermeasures. • PMCprimo C2, PMCprimo MC: Installation of Firmware Version 03.08.00 This update does not resolve the vulnerabilities (CVE-2021-34595, CVE-2021-34596, CVE-2021-34593, CVE-2021-30186, CVE-2021-30188, CVE-2021-30195, CVE-2019-19789) in the CODESYS V2 runtime system. The V2 runtime system is still included for compatibility reasons but is no longer supported by Pilz. Please migrate your application to the V3 runtime system or follow the general countermeasures.

  • FixedPMC programming tool 3.x.xpilz_psirt

    Installation of the software version 3.5.17

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10festo_psirt

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationPMC programming tool 3.x.xpilz_psirt

    Use a hardware firewall, host-based firewall or comparable measures at network level toprotect against unauthorised network communication with the PC. Use a virus scanner or other measures to protect against malware. Only use CODESYS libraries and archives from trusted sources.

  • MitigationFesto Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-D (All versions)cisa_csaf_ot

    (CVE-2020-12068, CVE-2022-22515, CVE-2022-22514, CVE-2022-22513, CVE-2021-36763, CVE-2021-33485, CVE-2020-10245, CVE-2020-15806, CVE-2019-9011, CVE-2019-9013, CVE-2020-12067, CVE-2020-12069, CVE-2021-36764, CVE-2019-5105, CVE-2021-29241, CVE-2021-29242, CVE-2022-22519, CVE-2022-22517, CVE-2018-0739) (Product Group: Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-D(All versions), Festo Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-LK(All versions), Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-S(All versions)): No fix planned. This issue will be handled with next hardware generation release.

  • MitigationFesto Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-S (All versions)cisa_csaf_ot

    (CVE-2020-12068, CVE-2022-22515, CVE-2022-22514, CVE-2022-22513, CVE-2021-36763, CVE-2021-33485, CVE-2020-10245, CVE-2020-15806, CVE-2019-9011, CVE-2019-9013, CVE-2020-12067, CVE-2020-12069, CVE-2021-36764, CVE-2019-5105, CVE-2021-29241, CVE-2021-29242, CVE-2022-22519, CVE-2022-22517, CVE-2018-0739) (Product Group: Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-D(All versions), Festo Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-LK(All versions), Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-S(All versions)): No fix planned. This issue will be handled with next hardware generation release.

  • MitigationFesto Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-LK (All versions)cisa_csaf_ot

    (CVE-2020-12068, CVE-2022-22515, CVE-2022-22514, CVE-2022-22513, CVE-2021-36763, CVE-2021-33485, CVE-2020-10245, CVE-2020-15806, CVE-2019-9011, CVE-2019-9013, CVE-2020-12067, CVE-2020-12069, CVE-2021-36764, CVE-2019-5105, CVE-2021-29241, CVE-2021-29242, CVE-2022-22519, CVE-2022-22517, CVE-2018-0739) (Product Group: Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-D(All versions), Festo Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-LK(All versions), Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-S(All versions)): No fix planned. This issue will be handled with next hardware generation release.

  • MitigationFesto Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-S (All versions)cisa_csaf_ot

    (CVE-2020-12068, CVE-2022-22515, CVE-2022-22514, CVE-2022-22513, CVE-2021-36763, CVE-2021-33485, CVE-2020-10245, CVE-2020-15806, CVE-2019-9011, CVE-2019-9013, CVE-2020-12067, CVE-2020-12069, CVE-2021-36764, CVE-2019-5105, CVE-2021-29241, CVE-2021-29242, CVE-2022-22519, CVE-2022-22517, CVE-2018-0739) (Product Group: Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-D(All versions), Festo Firmware (R06 (11.10.2016) = 2.3.8.1) installed on Festo Hardware Controller CECC-LK(All versions), Festo Firmware (R05 (17.06.2016) = 2.3.8.0) installed on Festo Hardware Controller CECC-S(All versions)): No fix planned. This issue will be handled with next hardware generation release.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • MitigationFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10cisa_csaf_ot

    Starting from Festo Automation Suite version 2.8.0.138, Codesys is no longer bundled with the suite and must be downloaded and installed separately by the customer. To mitigate this vulnerability customers are advised to: Download the latest, patched version of Codesys directly from the official Codesys website. Follow the installation and update instructions provided by Codesys to ensure all security fixes are applied. Regularly monitor Codesys security advisories and apply updates promptly. Maintain the Festo Automation Suite connector up to date by installing FAS updates as released by Festo.

  • No fix plannedfesto_psirt

    For CVE-2019-5105, CVE-2019-9011, CVE-2019-9013, CVE-2020-10245, CVE-2020-12067, CVE-2020-12068, CVE-2020-12069, CVE-2020-15806, CVE-2021-29241, CVE-2021-29242, CVE-2021-33485, CVE-2021-36763, CVE-2021-36764, CVE-2022-22513, CVE-2022-22514, CVE-2022-22515, CVE-2022-22517, CVE-2022-22519: No fix planned. This issue will be handled with next hardware generation release.

  • No fix plannedfesto_psirt

    No fix planned. This issue will be handled with next hardware generation release.

02

cvss

Technical severity, 0–10. One row per scoring source.

7.5
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 5–7.5

v2.05mediumAV:N/AC:L/Au:N/C:N/I:N/A:Pprimary · NVD / NIST USexploitability 10 · impact 2.9
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hprimary · NVD / NIST USexploitability 3.9 · impact 3.6
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · CISA US
v3.17.5highAV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · FSTEC (BDU) RU
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Pilz PSIRT DE
v3.17.5highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:Hsecondary · Festo PSIRT DE
v3.16.9mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:Usecondary · CVSS-BT (t0sche)
03

weaknesses

The CWE weakness classes this flaw belongs to.

04

affected products (34)

Products and version ranges known to be affected.

showing 20 of 34
05

advisories (7)

Vendor and ecosystem advisories describing this.

  • FSA-202202Festo: Controller CECC-S,LK,D family <= 2.3.8.1 - multiple vulnerabilities in CODESYS V3 runtime system2022-07-18csaf · festo_psirtDE

    The Festo controller CECC product family is affected by multiple vulnerabilities in the CODESYS V3 runtime.

  • FSA-202203Festo: Controller CECC-S,LK,D family firmware 2.4.2.0 - multiple vulnerabilities in CODESYS V3 runtime system2022-07-18csaf · festo_psirtDE

    The Festo controller CECC product family in firmware version 2.4.2.0 is affected by multiple vulnerabilities in the CODESYS V3 runtime.

  • FSA-202601Several CODESYS vulnerabilities in Festo Automation Suite2026-02-26csaf · festo_psirtDE

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

  • VDE-2021-054Pilz: Multiple vulnerabilities in CODESYS V2 and V3 runtime system2022-04-26csaf · pilz_psirtDE

    Several Pilz products use Versions V2 and V3 of the CODESYS runtime system from CODESYS GmbH, which enables the execution of IEC 61131-3 PLC programs. These runtime environments contain several vulnerabilities, which an attacker can exploit via the network. Successful exploitation of the vulnerabilities results in reduced availability and, in a worst case, to the insertion of program code.

  • VDE-2021-061Pilz: PMC programming tool 3.x.x affected by multiple vulnerabilities2022-04-26csaf · pilz_psirtDE

    The software product PMC programming tool from Pilz is based on the software CODESYS Development System from CODESYS GmbH. This software is affected by several vulnerabilities, which an attacker can exploit locally or via the network. This means that, in a worst case, attackers could execute arbitrary program code on the PC on which the PMC programming tool is used.

  • ICSA-25-273-04Festo Controller CECC-S,-LK,-D Family Firmware (Update A)2025-09-30icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities could allow an attacker to crash services, escalate privileges, bypass authentication, or gain unauthorized access to sensitive systems and data.

  • ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26icsa · cisa_csaf_otUS

    Starting with Festo Automation Suite (FAS) version 2.8.0.138, the suite is delivered only with a connector to Codesys, rather than including Codesys directly. Prior to this version, Codesys was bundled within the FAS installation. From version 2.8.0.138 onwards, customers are required to download and install Codesys independently. This change impacts the handling of security vulnerabilities (CVEs) related to Codesys. Any Codesys-related security issues must now be addressed by the customer through their separate Codesys installation. The FAS itself includes only the connector component, which is maintained and updated within the suite. Please ensure that Codesys is kept up to date independently to mitigate any potential security risks associated with the Codesys software.

06

also known as (4)

Other names and identifiers for this entity.

07

sources

Which sources assert this record, and when.

09

references (4)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan