CVE-2021-22779

mediumpriority · track · 36EPSS 0.011 · 64 %ileEURUUS
grimoire priorityP3 · Track
Exploitable?
—
no known exploitation
Likely / severe?
1.05% (64th) EPSS
CVSS 6.4 · medium
Is it mine?
53 products
Check your exposure
Who says so?
4 sources
cnnvd · enisa_euvd · fstec_bdu · cisa_csaf_ot

EPSS · scored 2026-10-27

Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.

01

remediations

Vendor fix, mitigation, or workaround guidance, as published by each source.

No vendor fix yet; a mitigation is available.

02

cvss

Technical severity, 0–10. One row per scoring source.

9.8
010

base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–critical · 6.4–9.8

v2.06.4mediumAV:N/AC:L/Au:N/C:P/I:P/A:Nprimary · NVD / NIST USexploitability 10 · impact 4.9
v3.19.1criticalCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Nprimary · NVD / NIST USexploitability 3.9 · impact 5.2
v3.09.8criticalCVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Hsecondary · CISA US
v3.19.1criticalAV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:Nsecondary · FSTEC (BDU) RU
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:Nsecondary · ENISA EU
v3.16.5mediumCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:Nsecondaryexploitability 3.9 · impact 2.5
v3.18.3highCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N/E:Usecondary · CVSS-BT (t0sche)
03

ssvc

A stakeholder decision — act, attend, or track — from exploitation and impact.

Exploitation: none · Automatable: yes · Technical Impact: partialcoordinatorcisa_ssvcUS
04

weaknesses

The CWE weakness classes this flaw belongs to.

05

affected products (53)

Products and version ranges known to be affected.

showing 20 of 53
06

advisories (1)

Vendor and ecosystem advisories describing this.

  • ICSA-21-194-02Schneider Electric Modicon Controllers and Software (Update A)2021-07-13icsa · cisa_csaf_otUS

    Successful exploitation of these vulnerabilities may allow arbitrary code execution and loss of confidentiality and integrity of the project file.

07

also known as (4)

Other names and identifiers for this entity.

08

sources

Which sources assert this record, and when.

09

references (5)

External citations — patches, advisories, analysis.

scry

Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.

Free scan