CVE-2019-6833
mediumpriority · track · 26EPSS 0.010 · 64 %ileEURUUSEPSS · scored 2026-10-28
A CWE-754 – Improper Check for Unusual or Exceptional Conditions vulnerability exists in Magelis HMI Panels (all versions of - HMIGTO, HMISTO, XBTGH, HMIGTU, HMIGTUX, HMISCU, HMISTU, XBTGT, XBTGT, HMIGXO, HMIGXU), which could cause a temporary freeze of the HMI when a high rate of frames is received. When the attack stops, the buffered commands are processed by the HMI panel.
remediations
Vendor fix, mitigation, or workaround guidance, as published by each source.
No vendor fix yet; a mitigation is available.
- MitigationMagelis HMIGTO seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMIGTU seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMIGTUX seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMIGXO seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMIGXU seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMISCU seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMISTO seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis HMISTU seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis XBTGC seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis XBTGH seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
- MitigationMagelis XBTGT seriescisa_csaf_ot
Schneider Electric recommends users set up network segmentation and implement a firewall to block all unauthorized access to Ports 44818/TCP, 502/TCP, 6000/TCP, 6002/TCP, 8080/TCP, 8014/TCP, and 6001/TCP.
cvss
Technical severity, 0–10. One row per scoring source.
base score 0–10 · higher = more severe · hover a vector to decode⚠ sources disagree · medium–high · 4.3–7.4
ssvc
A stakeholder decision — act, attend, or track — from exploitation and impact.
weaknesses
The CWE weakness classes this flaw belongs to.
affected products (42)
Products and version ranges known to be affected.
advisories (1)
Vendor and ecosystem advisories describing this.
- ICSA-20-044-02Schneider Electric Magelis HMI Panels2020-02-13icsa · cisa_csaf_otUS
Successful exploitation of this vulnerability could allow a denial-of-service condition.
also known as (4)
Other names and identifiers for this entity.
sources
Which sources assert this record, and when.
references (8)
External citations — patches, advisories, analysis.
- https://nvd.nist.gov/vuln/detail/CVE-2019-6833cnnvd
- https://security.cse.iitk.ac.in/responsible-disclosurecnnvd
- https://www.auscert.org.au/bulletins/ESB-2020.0525/cnnvd
- https://www.schneider-electric.com/ww/en/download/document/SEVD-2019-225-01cnnvd
- https://security.cse.iitk.ac.in/responsible-disclosureenisa_euvd
- https://www.schneider-electric.com/ww/en/download/document/SEVD-2019-225-01enisa_euvd
- https://security.cse.iitk.ac.in/responsible-disclosurenvd
- https://www.schneider-electric.com/ww/en/download/document/SEVD-2019-225-01Vendor Advisorynvd
Attackers weaponise vulnerabilities like this against internet-exposed services. See what is exposed on your perimeter with a free passive scan.
Free scan